Permit Information
Permit NumberBLD05-01604
StatusFinaled
Name ALPINE REAL ESTATE LLP
Site Address 12550 W EXPLORER DR Unit: 200
Project NameALPINE BLDG-2ND FLR
Customer Number 
ePlanReviewNo
Description
(ALPINE REAL ESTATE LLP)(ALPINE BLDG-STE 200) To construct a 6,322 sq.ft. office tenant located on the second floor, in a new shell building per approved plans. The shell & core was permitted under Bld04-02346. Work to include, construction of new interior partitions, installation of suspended ceiling system and related lighting, connect to existing HVAC system and install new ducting and registers, Miscelaneous related interior finishes counters and cabinets. This building is fully fire sprinklered any alterations to the sprinkler system shall be per NFPA #13 as regulated by the fire department. (Rmh)
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
BLD-Final5/10/20065/10/20065/10/2006PPASS
DetailsJim Sly
Scheduled by a contractor via Hello! on 5/10/2006 at 8:14:37 AM. Contact: ###-####.
C/C issued
DOC - Permit Finaled5/10/20065/10/20065/10/2006PPASS
DetailsJim Sly
Permanent Occupancy 5/10/20065/10/2006 DONE
Details
Permanent Occupancy 5/10/20065/10/2006 DONE
Details
Code Occupancy Approval  5/10/2006  
FIRE-Final Inspection1/12/20061/13/20061/13/2006APASS
DetailsTroy Cobbley
life safety finaled
BLD-Final12/30/20051/3/20061/3/2006APART
DetailsJim Sly
Scheduled by a contractor via Hello! on 12/30/2005 at 1:10:02 PM. Contact: ###-####.
OK for Temp Occ..........OK for Perm Occ when Fire Perms.
FIRE-Final Inspection12/30/200512/30/200512/30/2005PPART
DetailsTroy Cobbley
A temporary occupancy was given with Dave Hanneman's permission. Items needing addressing are syncing of the horns, mount map at facp, reverify signals (zone 10), and get the resubmitted plans approved.
FIRE-Final Inspection12/29/200512/29/200512/29/2005PFAIL
DetailsTroy Cobbley
Plug sprinkler heads mounted horizontally in the T.I. space. Reinstall the ball drip at the FDC. Certify the backflow preventor. Relocate the bell to the FDC. Provide above ground hydro test papers. Resubmit fire alarm plans showing the flow switch and tamper switch. Test all of the a/v's. Test all of the elevator functions/recall. Test the access controlled egress doors. Provide map at the FACP. Provide printout of the fire alarm signals. Provide minimum 8.3 AH batteries for the FACP. Life safety is ok to final when all of this is done.
BLD-Other12/2/200512/2/200512/2/2005PPASS
DetailsJim Sly
mike Note: ceiling grid; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles
Grid ok
BLD-Framing/Rough-in10/11/200510/11/200510/11/2005PPASS
DetailsMike Jordan
mike; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa