BLD-Final | 12/2/2005 | 12/2/2005 | 12/2/2005 | P | PASS |
Mike Jordan
|
|
|
Door hardware downstairs ok. All others finaled. Ok for perm occ.
|
Permanent Occupancy | | 12/2/2005 | 12/2/2005 | | DONE |
|
|
|
|
BLD-Final | 11/1/2005 | 11/2/2005 | 11/2/2005 | P | PART |
Mike Jordan
|
|
|
pat; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa. Ok for temp occ at upstairs only. Door hardware to be changed out in basement. Elec. and plumbing finals still need completed, temps only.
|
FIRE-Final Inspection | 11/1/2005 | 11/2/2005 | 11/2/2005 | A | PASS |
Troy Cobbley
|
|
|
life safety finaled
|
BLD-Final | 10/31/2005 | 11/1/2005 | 11/1/2005 | P | NR |
Jim Sly
|
|
|
pat; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa
|
FIRE-Final Inspection | 10/31/2005 | 11/1/2005 | 11/1/2005 | A | FAIL |
Troy Cobbley
|
|
|
The duct smoke detector on the left side as you enter the room operated correctly but the duct detector on the right side did not operate correctly. Still need the hardware for doors in the basement.
|
BLD-Final | 10/28/2005 | 10/31/2005 | 10/31/2005 | P | NR |
Jim Sly
|
|
|
pat; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa Need fire
|
FIRE-Final Inspection | 10/28/2005 | 10/31/2005 | 10/31/2005 | A | FAIL |
Troy Cobbley
|
|
|
Duct detectors still need connected and tested. Also need the door hardware in the basement installed.
|
FIRE-Final Inspection | 10/27/2005 | 10/28/2005 | 10/28/2005 | P | CANC |
Troy Cobbley
|
|
|
Not ready
|
BLD-Final | 10/25/2005 | 10/26/2005 | 10/26/2005 | P | NR |
Jim Sly
|
|
|
pat; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa
|
FIRE-Final Inspection | 10/25/2005 | 10/26/2005 | 10/26/2005 | A | FAIL |
Troy Cobbley
|
|
|
Project not ready for inspection. Duct detectors not wired up yet, exit signs not working, extinguishers not mounted.
|
FIRE-Final Inspection | 10/7/2005 | 10/10/2005 | 10/10/2005 | P | FAIL |
Troy Cobbley
|
|
|
Inspection was actually for a conference. I went over life safety items with the contractor. This included providing an additional exit sign at the bottom of the stairs with approved door hardware on the second exit to the exterior stairway. Also needs automatic flush bolts on the main entry exit. The two interior doors that lead into the main exit lobby require approved door hardware unless plan review is ok with the thumbturn deadbolts. Fire extinguishers will be required on both levels as well.
|
BLD-Conference | 10/6/2005 | 10/7/2005 | 10/7/2005 | P | DONE |
Jim Sly
|
|
|
chris; Phone #: ###-#### Internet Inspection Request from: Barbara Moore
|
BLD-Framing/Rough-in | 9/15/2005 | 9/16/2005 | 9/16/2005 | A | PASS |
Mike Jordan
|
|
|
###-#### - chris
|
BLD-Framing/Rough-in | 9/1/2005 | 9/6/2005 | 9/6/2005 | A | PASS |
Jim Sly
|
|
|
Scheduled by a contractor via Hello! on 9/1/2005 at 10:56:05 AM. Contact: ###-####. Ustick and milwalkee.....Parking lot just East of Regies Vegies
|