BLD-Final | 11/18/2005 | 11/23/2005 | 11/23/2005 | P | PASS |
Tom Arcoraci
|
|
|
ryan ; Phone #: ###-####//please check if mechanical permit needed for this project// Internet Inspection Request from: Marsha mech permit not required non done
|
FIRE-Final Inspection | 11/22/2005 | 11/23/2005 | 11/23/2005 | A | PASS |
Forrest France
|
|
|
c/n items have been completed, life safety passed.
|
Permanent Occupancy | | 11/23/2005 | 11/23/2005 | | DONE |
|
|
|
|
FIRE-Final Inspection | 11/22/2005 | 11/22/2005 | 11/22/2005 | P | NR |
Forrest France
|
|
|
c/n not 100% completed yet per contractor.
|
FIRE-Final Inspection | 11/18/2005 | 11/22/2005 | 11/22/2005 | A | NR |
Forrest France
|
|
|
Per contractor phone call, not all items on the correction notice have been completed.
|
FIRE-Final Inspection | 11/17/2005 | 11/18/2005 | 11/18/2005 | A | FAIL |
Forrest France
|
|
|
Remove surface bolts and door stopper at back double doors, lower the provided fire ext. to 48" max AFF,one bulb at emergency light is out, provide visual indicator at main entry/exit door, post max occupant sign, no storage allowed in the break room, duct smoke detectors may be required at AHU's.
|
BLD-Final | 11/17/2005 | 11/18/2005 | 11/18/2005 | P | CANC |
Dave Hannah
|
|
|
ryan; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles Inspection cancelled from web by: Marsha Smylie
|
BLD-Framing/Rough-in | 11/8/2005 | 11/9/2005 | 11/9/2005 | A | PART |
Dave Hannah
|
|
|
lloyd; Phone #: ###-#### Note: please call 1/2 hr prior to inpspection Internet Inspection Request from: Cathy Chiles 2hr wall sep in attic ok to install ceiling
|
BLD-Framing/Rough-in | 10/24/2005 | 10/25/2005 | 10/25/2005 | A | FAIL |
Jim Storey
|
|
|
lloyd; Phone #: ###-#### Note: please call 1/2 hr prior to inspection Internet Inspection Request from: Cathy Chiles
|