BLD-Final | 1/10/2006 | 1/10/2006 | 1/10/2006 | P | PASS |
Mike Jordan
|
|
|
robert; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa. Ok for perm occ. New doors installed with automatic flush bolts and indicator.
|
Permanent Occupancy | | 1/10/2006 | 1/10/2006 | | DONE |
|
|
|
|
BLD-Final | 11/7/2005 | 11/7/2005 | 11/7/2005 | P | PEND |
Mike Jordan
|
|
|
Temp occ given. Needs final from mech. Also needs to install code compliant locks on doors. Contractor has ordered new doors. Existing doors have been approved gor use by G. Slane as long as doors are able to be locked in an open position while store is open for bussiness. Temporary latches have been installed in the floor allowing the door to be locked in the open position.
|
BLD-Final | 11/1/2005 | 11/3/2005 | 11/3/2005 | P | FAIL |
Mike Jordan
|
|
|
robert; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa. Incorrect locking mechanism on paired egress doors.
|
FIRE-Final Inspection | 11/1/2005 | 11/3/2005 | 11/3/2005 | A | PASS |
Troy Cobbley
|
|
|
Life safety finaled
|
FIRE-Final Inspection | 11/2/2005 | 11/2/2005 | 11/2/2005 | P | FAIL |
Troy Cobbley
|
|
|
robert; Phone #: ###-#### The only life safety items ready to look at was the smoke control and the duct smoke detectors of which both passed. Exit signs to and in the rear corridor did not work. Needs an additional fire extinguisher.
|
BLD-Framing/Rough-in | 10/11/2005 | 10/11/2005 | 10/11/2005 | A | PART |
Jim Storey
|
|
|
Scheduled by a contractor via Hello! on 10/11/2005 at 7:06:21 AM. Contact: ###-####.coridor ok for cover as well as west fur out wall.1 hr
|
BLD-Framing/Rough-in | 10/6/2005 | 10/7/2005 | 10/7/2005 | A | PART |
Jim Sly
|
|
|
robert; Phone #: ###-#### Internet Inspection Request from: Barbara Moore Partial framing ...storefront, restrooms, corridor, partition walls OK. Discussed issues with framer about continuity of 1hr fire partition walls between tenants. Have not framed wall between existing 2hr stair tower and new 1hr corridor.....This will cause a problem with transition from 2hr to 1hr rating.....Need continuous membrane in these areas for rating.... Need to call for inspections as needed and not cover areas effected until we inspect them. Need to verify existing Fire partition walls are fire stopped floor to roof deck.
|
BLD-Framing/Rough-in | 10/5/2005 | 10/6/2005 | 10/6/2005 | P | DEFR |
Jim Storey
|
|
|
robert; Phone #: ###-#### Internet Inspection Request from: Barbara Moore out of time rolled to am.
|