BLD-Final | 2/2/2007 | 2/5/2007 | 2/5/2007 | P | PASS |
Tom Arcoraci
|
|
|
DERRICK; Phone #: ###-#### Internet Inspection Request from: Victoria Beall
|
FIRE-Final Inspection | 2/2/2007 | 2/2/2007 | 2/2/2007 | P | PASS |
Troy Cobbley
|
|
|
Life safety finaled
|
BLD-Aging Inspection | 1/19/2007 | 1/19/2007 | 1/19/2007 | | NR |
Tom Arcoraci
|
|
|
|
FIRE-Conference | 11/15/2006 | 11/16/2006 | 11/16/2006 | A | PASS |
Troy Cobbley
|
|
|
The owners representative wanted me to ok their new layout to meet the sprinkler analasis. They are reinstalling the racks starting in the northwest corner. They are providing 6" transverse and longitudinal flu spaces with 48" isles. This meets the intent of the letter and if carried out will be approved by me.
|
BLD-Aging Inspection | 9/19/2006 | 9/19/2006 | 9/21/2006 | | NR |
Troy Cobbley
|
|
|
work is in progrss
|
FIRE-Final Inspection | 9/20/2006 | 9/20/2006 | 9/20/2006 | P | FAIL |
Troy Cobbley
|
|
|
All items appear to be provided and corrected except for the 6" flu space required per the letter from Treasure Valley Fire Protection. Contractor is going to set up a conference with Sam Rogers.
|
FIRE-Final Inspection | 5/19/2006 | 5/19/2006 | 5/19/2006 | P | FAIL |
Troy Cobbley
|
|
|
Plan review comments had not been followed as far as providing verification of the existing sprinkler systems design parameters. No real inspection done. Just went over what I will need for the next inspection.
|
BLD-Aging Inspection | 3/6/2006 | 3/6/2006 | 3/6/2006 | | NR |
Tom Arcoraci
|
|
|
|