BLD-Conference | 11/1/2007 | 11/1/2007 | 11/1/2007 | P | PASS |
Tony Young
|
|
|
Steve; Phone #: ###-#### permit is ok for full c of o
|
BLD-Final | 10/18/2007 | 10/18/2007 | 10/18/2007 | P | PASS |
Tony Young
|
|
|
steve Phone #: ###-#### ok for perm occ. on this section of building
|
FIRE-Final Inspection | 10/8/2007 | 10/9/2007 | 10/9/2007 | A | PASS |
Forrest France
|
|
|
Fire life safety finaled.
|
BLD-Final | 10/5/2007 | 10/8/2007 | 10/8/2007 | A | PART |
Tony Young
|
|
|
kirt Phone #: ###-#### ok pending others
|
BLD-Final | 8/31/2006 | 9/5/2006 | 9/5/2006 | A | PART |
Dave Hannah
|
|
|
steve; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley ok to use ada rest rooms
|
FIRE-Final Inspection | 8/31/2006 | 9/1/2006 | 9/1/2006 | A | PART |
Forrest France
|
|
|
Inspection for the remodeled restrooms and one adjacent confrence room is satisfactory, final pending project related fire sprinkler permit final.
|
BLD-Framing/Rough-in | 7/26/2006 | 7/26/2006 | 7/26/2006 | P | PART |
Dave Hannah
|
|
|
Curt ###-#### rest room wall in basement ok to cover
|
BLD-Framing/Rough-in | 7/25/2006 | 7/26/2006 | 7/26/2006 | A | CANC |
Tony Young
|
|
|
curt; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley out of time,, rescheduled for pm
|
BLD-Framing/Rough-in | 7/10/2006 | 7/10/2006 | 7/10/2006 | P | PART |
Dave Hannah
|
|
|
curt; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley ok to cover basement shower rooms
|
FIRE-Conference | 5/22/2006 | 5/25/2006 | 5/26/2006 | P | PART |
Forrest France
|
|
|
Inspection to verify completion of previous correction notice items, also tested access controlled atrium doors on floors 1-5 for functionality, tested emergency lighting and exit signage on backup power for the basement only, verified mag lock dropout upon fire alarm at access controlled doors, tested door release at basement elevator lobby. The project related fire sprinkler permit must be finaled prior to final approval for the basement code upgrade permit.
|
FIRE-Conference | 5/12/2006 | 5/19/2006 | 5/19/2006 | P | CANC |
Troy Cobbley
|
|
|
Per the contractor this conference had been canceled earlier.
|
BLD-Conference | 5/8/2006 | 5/9/2006 | 5/9/2006 | A | DONE |
Dave Hannah
|
|
|
curt; Phone #: ###-#### Internet Inspection Request from: Rita DeYoung
|
FIRE-Conference | 5/4/2006 | 5/5/2006 | 5/5/2006 | A | PART |
Forrest France
|
|
|
Some items on correction notice have been completed including door hardware, fire ext., occupant load sign, fire sprinkler. Need to provide directional arrow at the exit sign adjacent to the SW exit stairs, remove clasp for surface lock at the pantry, provide occupant load sign in the meeting room. Still need to verify emergency lighting and exit sign illumination for the path of egress, and door lock dropout upon fire alarm activation.
|
FIRE-Conference | 5/3/2006 | 5/4/2006 | 5/4/2006 | A | NR |
Forrest France
|
|
|
Field inspection to be scheduled for 5/5 in the AM as agreed.
|
BLD-Conference | 5/3/2006 | 5/3/2006 | 5/3/2006 | P | PART |
Dave Hannah
|
|
|
kirt; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles walked basement found several doors that need tobe up graded to 90 min also need to talk to jason about 2hr walls
|
BLD-Final | 4/24/2006 | 4/26/2006 | 4/26/2006 | A | FAIL |
Tony Young
|
|
|
Gary ; Phone #: ###-#### Internet Inspection Request from: Rita DeYoung need trades 1st,, no inspection made
|
FIRE-Final Inspection | 4/24/2006 | 4/25/2006 | 4/26/2006 | P | FAIL |
Forrest France
|
|
|
Several issues need addressed as discussed on site regarding life safety inspection for the basement only including door hardware (knobs at stairway exits, manual flush bolts on inactive leafs, padlocks on cooler and storage rooms, missing closures and seals at rated room doors, etc.), exit signs at some areas are not illuminated or need relocation, fire extinguishers shall be mounted no higher than 48" AFF, some locations may be overspaced to the nearest FE (75' max travel), provide max occupant load sign for the meeting room, need to test emergency lighting for the path of egress, access controlled egress doors shall be tested for loss of power and alarm at the mag locks, provide smoke detection for the battery room (a HD appears to be installed), one 200 deg. QR head needs replaced as noted, per the upgrade agreement some required alarm and sprinkler issues related to the basement are not completed at this time. Not all items reviewed at this inspection, contractor to re-schedule when general noted issues have been corrected.
|