BLD-Final | 1/24/2007 | 1/25/2007 | 1/25/2007 | A | PASS |
Mike Jordan
|
|
|
jeff; Phone #: ###-#### Internet Inspection Request from: Victoria Beall
|
DOC - Permit Finaled | 1/25/2007 | 1/25/2007 | 1/25/2007 | P | PASS |
Mike Jordan
|
|
|
UL approved 1 hr attic access installed. Letter of compliance issued for shell and core. Bonded for landscape and public works.
|
BLD-Final | 12/27/2006 | 12/28/2006 | 12/28/2006 | A | PART |
Mike Jordan
|
|
|
jeff ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith. Ok for temp occ on shell. Needs to install 1hr rated UL listed attic access.
|
BLD-Final | 12/26/2006 | 12/27/2006 | 12/27/2006 | P | FAIL |
Mike Jordan
|
|
|
jeff ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith. Radiation damper required at fresh air duct at penetration at 1hr ceiling assembly. Provide UL listed 1hr attic access. Remove sheet metal patch at 1hr ceiling assembly . Must attach back to framing member.
|
FIRE-Final Inspection | 12/26/2006 | 12/27/2006 | 12/27/2006 | A | PASS |
Troy Cobbley
|
|
|
life safety finaled
|
FIRE-Final Inspection | 12/22/2006 | 12/26/2006 | 12/26/2006 | A | PASS |
Forrest France
|
|
|
Items on previous c/n are complete, shell life safety is acceptable.
|
FIRE-Final Inspection | 12/22/2006 | 12/22/2006 | 12/22/2006 | P | CANC |
Troy Cobbley
|
|
|
Per Jeff he wants to reschedule for next week.
|
Code Occupancy Approval Temp | | | 12/21/2006 | | DONE |
|
|
|
I WILL SIGN TEMPORARY WHEN BOND POSTED FOR $79278.66
|
FIRE-Final Inspection | 12/12/2006 | 12/12/2006 | 12/12/2006 | P | FAIL |
Troy Cobbley
|
|
|
Provide pavement, provide fire lane signage per sheet A1-1a, provide sticker at the main exit, provide remote annunciator and test the duct smoke detector and provide the fire dept. review comments for other possible requirements.
|
BLD-Conference | 12/11/2006 | 12/12/2006 | 12/12/2006 | A | DONE |
Mike Jordan
|
|
|
jeff; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles
|
BLD-Framing/Rough-in | 11/2/2006 | 11/2/2006 | 11/2/2006 | P | NR |
Mike Jordan
|
|
|
jeff ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith
|
BLD-Framing/Rough-in | 11/1/2006 | 11/1/2006 | 11/1/2006 | P | FAIL |
Mike Jordan
|
|
|
jeff; Phone #: ###-#### Internet Inspection Request from: Patricia Smith. Needs to box out elec panel box.
|
BLD-Framing/Rough-in | 10/27/2006 | 10/30/2006 | 10/30/2006 | A | NR |
Mike Jordan
|
|
|
kameron; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles. Needs to pull elec. permit for shell and get ri insp.
|
BLD-Aging Inspection | 10/4/2006 | 10/4/2006 | 10/4/2006 | | PASS |
Mike Jordan
|
|
|
wip
|
BLD-Framing/Rough-in | 7/19/2006 | 7/20/2006 | 7/20/2006 | P | PART |
Mike Jordan
|
|
|
cameron sheer nailing; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley. Roof nailing and hardware ok. Shear nailing on exterior perimeter walls ok. Simpson holddown straps were not installed. c/n posted. ok to cover roof.
|
BLD-Other | 7/5/2006 | 7/6/2006 | 7/6/2006 | A | PART |
Mike Jordan
|
|
|
MARK nOTE: SHEET WALL AND NAILING ; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles. 1hour seperation wall innner layer nailing pattern.
|
BLD-Footing | 6/5/2006 | 6/6/2006 | 6/6/2006 | A | PASS |
Mike Jordan
|
|
|
ed - reinsp; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley. peremeter footings. no special insp. is required.
|
BLD-Footing | 6/2/2006 | 6/5/2006 | 6/5/2006 | A | PART |
Mike Jordan
|
|
|
Phone #: ###-#### Internet Inspection Request from: Cathy Chiles. perimeter footings. Cpntractor to confirm special insp.
|