Permanent Occupancy | | 8/15/2006 | 8/15/2006 | | DONE |
|
|
|
|
BLD-Final | 6/6/2006 | 6/7/2006 | 6/7/2006 | P | PART |
Dave Hannah
|
|
|
gregg; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley ok for temp occ ok for perm occ after elec and mec sign perm
|
FIRE-Final Inspection | 6/6/2006 | 6/7/2006 | 6/7/2006 | A | PASS |
Forrest France
|
|
|
The required corrections have been made and verified for completion, fire life safety passed inspection.
|
BLD-Final | 6/5/2006 | 6/6/2006 | 6/6/2006 | P | CANC |
Dave Hannah
|
|
|
GREG; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles
|
FIRE-Final Inspection | 6/5/2006 | 6/6/2006 | 6/6/2006 | A | FAIL |
Forrest France
|
|
|
Need to provide a fire extinguisher with current tag installed as discussed, one exit sign is blocked and will need to be relocated, door hardware at one location will need to be changed, still need to test emergency lighting for the path of egress.
|
BLD-Final | 5/26/2006 | 5/30/2006 | 5/31/2006 | P | NR |
Dave Hannah
|
|
|
greg 5th floor; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles needs fire life saftey final
|
FIRE-Final Inspection | 5/26/2006 | 5/30/2006 | 5/30/2006 | A | CANC |
Troy Cobbley
|
|
|
greg 5th floor; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles
|
BLD-Final | 5/25/2006 | 5/26/2006 | 5/26/2006 | P | NR |
Dave Hannah
|
|
|
greg; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles
|
FIRE-Final Inspection | 5/25/2006 | 5/26/2006 | 5/26/2006 | A | NR |
Forrest France
|
|
|
No inspection done, the project related fire sprinkler permit must be requested for final inspection and approval before BLD life safety final can be granted.
|
BLD-Framing/Rough-in | 5/22/2006 | 5/23/2006 | 5/24/2006 | P | PART |
Dave Hannah
|
|
|
greg; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles ok to cover both sides of walls
|
FIRE-Conference | 4/26/2006 | 4/27/2006 | 4/27/2006 | A | DONE |
Forrest France
|
|
|
On site confrence to discuss field modification of office wall partition layout and the affected sprinkler, alarm notification, and exiting issues.
|