Code Occupancy Approval | | | 10/27/2009 | | DONE |
|
|
|
|
BLD-Final | 1/24/2008 | 1/24/2008 | 10/1/2008 | A | DONE |
Cathy Brown
|
|
|
|
Code Occupancy Approval | | | 4/14/2008 | | DONE |
|
|
|
All landscaping, buffering, curb and lot requirements met under BLD06-00456.
|
FIRE-Final Inspection | 2/14/2008 | 2/15/2008 | 2/15/2008 | A | PASS |
Forrest France
|
|
|
Items on correction notice verified for completion, fire life safety finaled.
|
BLD-Final | 2/12/2008 | 2/12/2008 | 2/12/2008 | P | PASS |
Tom Arcoraci
|
|
|
ok pending fire ok
|
FIRE-Final Inspection | 2/11/2008 | 2/12/2008 | 2/12/2008 | A | PART |
Forrest France
|
|
|
Fire life safety final pending fire department access lane curb marking per fire code review notes and provision of missing max. occupant load signs at three areas (pool room, patio area, exercise room) -see review notes for details. Remainder of fire life safety is satisfactory.
|
BLD-Conference | 2/4/2008 | 2/4/2008 | 2/4/2008 | A | PASS |
Tom Arcoraci
|
|
|
|
BLD-Conference | 1/30/2008 | 1/31/2008 | 1/31/2008 | A | CANC |
Tom Arcoraci
|
|
|
|
Code Occupancy Approval | 1/28/2008 | 1/28/2008 | 1/29/2008 | P | PASS |
Joe R Venneman
|
|
|
|
Code Occupancy Approval Temp | 1/28/2008 | 1/28/2008 | 1/28/2008 | P | PASS |
Joe R Venneman
|
|
|
Contractor posted bond for unfinished landscaping - bid was for $26,031 + 10%.
|
BLD-Conference | 1/25/2008 | 1/28/2008 | 1/28/2008 | A | PASS |
Tom Arcoraci
|
|
|
|
Code Occupancy Approval Temp | | | 1/28/2008 | | DONE |
|
|
|
|
BLD-Wall cover | 1/25/2008 | 1/25/2008 | 1/25/2008 | P | PASS |
Tom Arcoraci
|
|
|
|
FIRE-Final Inspection | 1/24/2008 | 1/25/2008 | 1/25/2008 | A | NR |
Forrest France
|
|
|
Need project related fire alarm and sprinkler permit final inspections and approvals prior to building life safety final.
|
BLD-Conference | 1/15/2008 | 1/15/2008 | 1/16/2008 | P | PASS |
Tom Arcoraci
|
|
|
|
BLD-Conference | 1/14/2008 | 1/15/2008 | 1/15/2008 | A | CANC |
Tom Arcoraci
|
|
|
|
BLD-Framing/Rough-in | 1/11/2008 | 1/11/2008 | 1/11/2008 | P | PASS |
Tom Arcoraci
|
|
|
|
BLD-Conference | 1/4/2008 | 1/4/2008 | 1/4/2008 | P | PASS |
Tom Arcoraci
|
|
|
|
BLD-Wall cover | 12/31/2007 | 12/31/2007 | 12/31/2007 | P | PASS |
Tom Arcoraci
|
|
|
jack
|
BLD-Other | 12/28/2007 | 12/28/2007 | 12/28/2007 | P | PASS |
Tom Arcoraci
|
|
|
|
BLD-Wall cover | 12/27/2007 | 12/28/2007 | 12/28/2007 | A | PASS |
Tom Arcoraci
|
|
|
|
BLD-Wall cover | 12/24/2007 | 12/24/2007 | 12/24/2007 | P | CANC |
Tom Arcoraci
|
|
|
|
BLD-Conference | 12/12/2007 | 12/12/2007 | 12/12/2007 | P | PASS |
Tom Arcoraci
|
|
|
|
BLD-Wall cover | 12/11/2007 | 12/11/2007 | 12/11/2007 | P | PASS |
Tom Arcoraci
|
|
|
|
BLD-Wall cover | 12/10/2007 | 12/11/2007 | 12/11/2007 | A | CANC |
Tom Arcoraci
|
|
|
|
BLD-Wall cover | 11/27/2007 | 11/27/2007 | 11/27/2007 | P | PASS |
Tom Arcoraci
|
|
|
|
BLD-Wall cover | 11/16/2007 | 11/16/2007 | 11/16/2007 | P | PASS |
Tom Arcoraci
|
|
|
|
BLD-Wall cover | 11/9/2007 | 11/9/2007 | 11/9/2007 | P | PASS |
Tom Arcoraci
|
|
|
jack
|
BLD-Wall cover | 11/7/2007 | 11/7/2007 | 11/8/2007 | P | PASS |
Tom Arcoraci
|
|
|
jack
|
BLD-Wall cover | 11/2/2007 | 11/2/2007 | 11/2/2007 | P | PASS |
Tom Arcoraci
|
|
|
|
BLD-Wall cover | 10/26/2007 | 10/26/2007 | 10/26/2007 | P | PASS |
Tom Arcoraci
|
|
|
|
BLD-Framing/Rough-in | 10/23/2007 | 10/23/2007 | 10/23/2007 | P | PASS |
Tom Arcoraci
|
|
|
see jack
|
BLD-Wall cover | 10/19/2007 | 10/19/2007 | 10/19/2007 | P | PASS |
Tom Arcoraci
|
|
|
|
BLD-Wall cover | 10/16/2007 | 10/16/2007 | 10/16/2007 | P | PASS |
Tom Arcoraci
|
|
|
|
BLD-Wall cover | 10/4/2007 | 10/4/2007 | 10/4/2007 | P | PASS |
Tom Arcoraci
|
|
|
|
BLD-Other | 10/2/2007 | 10/3/2007 | 10/3/2007 | P | PASS |
Tom Arcoraci
|
|
|
|
BLD-Wall cover | 10/2/2007 | 10/2/2007 | 10/2/2007 | P | PASS |
Tom Arcoraci
|
|
|
ip ok
|
BLD-Wall cover | 9/25/2007 | 9/25/2007 | 9/25/2007 | P | PASS |
Tom Arcoraci
|
|
|
wip ok
|
BLD-Wall cover | 9/20/2007 | 9/21/2007 | 9/21/2007 | P | PASS |
Tom Arcoraci
|
|
|
1 st floor
|
BLD-Wall cover | 9/19/2007 | 9/19/2007 | 9/19/2007 | P | PASS |
Tom Arcoraci
|
|
|
1st floor
|
BLD-Wall cover | 9/17/2007 | 9/17/2007 | 9/17/2007 | P | PASS |
Tom Arcoraci
|
|
|
wip ok
|
BLD-Wall cover | 9/14/2007 | 9/14/2007 | 9/14/2007 | P | CANC |
Tom Arcoraci
|
|
|
|
BLD-Wall cover | 9/4/2007 | 9/4/2007 | 9/4/2007 | P | PASS |
Tom Arcoraci
|
|
|
|
BLD-Other | 8/30/2007 | 8/30/2007 | 8/31/2007 | P | PASS |
Tom Arcoraci
|
|
|
|
BLD-Wall cover | 8/28/2007 | 8/28/2007 | 8/28/2007 | P | PASS |
Tom Arcoraci
|
|
|
|
BLD-Other | 8/24/2007 | 8/24/2007 | 8/24/2007 | P | PASS |
Tom Arcoraci
|
|
|
|
BLD-Wall cover | 8/23/2007 | 8/23/2007 | 8/23/2007 | P | PASS |
Tom Arcoraci
|
|
|
wip ok
|
BLD-Wall cover | 8/16/2007 | 8/16/2007 | 8/16/2007 | P | PASS |
Tom Arcoraci
|
|
|
|
BLD-Other | 8/3/2007 | 8/6/2007 | 8/6/2007 | P | PASS |
Tom Arcoraci
|
|
|
|
BLD-Wall cover | 8/3/2007 | 8/3/2007 | 8/3/2007 | P | PASS |
Tom Arcoraci
|
|
|
|
BLD-Wall cover | 7/24/2007 | 7/24/2007 | 7/24/2007 | P | PASS |
Tom Arcoraci
|
|
|
wip ok shafts
|
BLD-Wall cover | 7/17/2007 | 7/17/2007 | 7/17/2007 | P | PASS |
Tom Arcoraci
|
|
|
wip ok
|
BLD-Other | 7/13/2007 | 7/13/2007 | 7/13/2007 | P | PASS |
Tom Arcoraci
|
|
|
wip ok
|
BLD-Wall cover | 7/12/2007 | 7/12/2007 | 7/12/2007 | P | PASS |
Tom Arcoraci
|
|
|
|
BLD-Wall cover | 7/6/2007 | 7/6/2007 | 7/6/2007 | P | PASS |
Tom Arcoraci
|
|
|
3 floor ok for cover
|
BLD-Wall cover | 7/3/2007 | 7/3/2007 | 7/3/2007 | P | PASS |
Tom Arcoraci
|
|
|
4 fl ok
|
BLD-Other | 6/27/2007 | 6/27/2007 | 6/27/2007 | P | PASS |
Tom Arcoraci
|
|
|
|
BLD-Wall cover | 6/20/2007 | 6/20/2007 | 6/20/2007 | P | PASS |
Tom Arcoraci
|
|
|
ok to cover 4 floor
|
BLD-Conference | 6/7/2007 | 6/7/2007 | 6/7/2007 | P | PASS |
Tom Arcoraci
|
|
|
|
BLD-Wall cover | 6/7/2007 | 6/7/2007 | 6/7/2007 | A | CANC |
Tom Arcoraci
|
|
|
|
BLD-Other | 6/1/2007 | 6/1/2007 | 6/1/2007 | P | PASS |
Tom Arcoraci
|
|
|
|
BLD-Wall cover | 5/24/2007 | 5/25/2007 | 5/25/2007 | P | PASS |
Tom Arcoraci
|
|
|
wip ok
|
BLD-Other | 5/21/2007 | 5/21/2007 | 5/21/2007 | P | PASS |
Tom Arcoraci
|
|
|
wip
|
BLD-Wall cover | 5/15/2007 | 5/15/2007 | 5/16/2007 | P | CANC |
Tom Arcoraci
|
|
|
|
BLD-Conference | 5/11/2007 | 5/11/2007 | 5/11/2007 | P | PASS |
Tom Arcoraci
|
|
|
|
BLD-Other | 5/4/2007 | 5/4/2007 | 5/4/2007 | P | PASS |
Tom Arcoraci
|
|
|
jack wip ok
|
BLD-Other | 5/1/2007 | 5/2/2007 | 5/2/2007 | A | PASS |
Tom Arcoraci
|
|
|
|
BLD-Wall cover | 4/25/2007 | 4/26/2007 | 4/26/2007 | P | PASS |
Tom Arcoraci
|
|
|
|
BLD-Other | 4/19/2007 | 4/24/2007 | 4/24/2007 | P | PASS |
Tom Arcoraci
|
|
|
|
BLD-Other | 4/16/2007 | 4/17/2007 | 4/18/2007 | P | CANC |
Tom Arcoraci
|
|
|
|
BLD-Other | 4/4/2007 | 4/10/2007 | 4/10/2007 | P | PASS |
Tom Arcoraci
|
|
|
wip ok
|
BLD-Wall cover | 4/3/2007 | 4/4/2007 | 4/4/2007 | P | PASS |
Tom Arcoraci
|
|
|
wip ok
|
BLD-Wall cover | 4/3/2007 | 4/3/2007 | 4/3/2007 | P | CANC |
Tom Arcoraci
|
|
|
|
BLD-Wall cover | 3/30/2007 | 3/30/2007 | 3/30/2007 | P | PASS |
Tom Arcoraci
|
|
|
|
BLD-Wall cover | 3/20/2007 | 3/20/2007 | 3/20/2007 | P | PASS |
Tom Arcoraci
|
|
|
see jack wip ok
|
BLD-Wall cover | 3/13/2007 | 3/14/2007 | 3/14/2007 | A | PASS |
Tom Arcoraci
|
|
|
stair and shaft discused
|
BLD-Framing/Rough-in | 3/12/2007 | 3/13/2007 | 3/13/2007 | A | PASS |
Tom Arcoraci
|
|
|
Scheduled by a contractor via Hello! on 3/12/2007 at 2:53:21 PM. Contact: ###-####. wip shear ok footing for piers ok
|
BLD-Wall cover | 3/12/2007 | 3/12/2007 | 3/13/2007 | P | PASS |
Tom Arcoraci
|
|
|
wip shear ok
|
BLD-Conference | 3/2/2007 | 3/2/2007 | 3/5/2007 | P | PASS |
Tom Arcoraci
|
|
|
|
BLD-Wall cover | 3/1/2007 | 3/1/2007 | 3/2/2007 | P | PASS |
Tom Arcoraci
|
|
|
|
BLD-Wall cover | 2/1/2007 | 2/1/2007 | 2/1/2007 | P | PASS |
Tom Arcoraci
|
|
|
|
BLD-Footing | 1/9/2007 | 1/10/2007 | 1/10/2007 | A | PASS |
Tom Arcoraci
|
|
|
jack; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles
|
BLD-Other | 1/9/2007 | 1/9/2007 | 1/9/2007 | P | PASS |
Tom Arcoraci
|
|
|
|
BLD-Footing | 1/3/2007 | 1/3/2007 | 1/3/2007 | P | PASS |
Tom Arcoraci
|
|
|
jack; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles
|
BLD-Conference | 12/21/2006 | 12/21/2006 | 12/21/2006 | P | CANC |
Tom Arcoraci
|
|
|
jack
|
BLD-Conference | 12/7/2006 | 12/8/2006 | 12/8/2006 | P | PASS |
Tom Arcoraci
|
|
|
see jack
|
BLD-Other | 11/27/2006 | 11/27/2006 | 11/27/2006 | P | PASS |
Tom Arcoraci
|
|
|
see jack
|
BLD-Other | 11/17/2006 | 11/17/2006 | 11/17/2006 | P | PASS |
Tom Arcoraci
|
|
|
see jack
|
BLD-Conference | 11/9/2006 | 11/9/2006 | 11/9/2006 | P | PASS |
Tom Arcoraci
|
|
|
|
BLD-Concrete | 11/7/2006 | 11/7/2006 | 11/7/2006 | P | PASS |
Tom Arcoraci
|
|
|
|
BLD-Footing | 10/13/2006 | 10/16/2006 | 10/16/2006 | P | PASS |
Tom Arcoraci
|
|
|
jack; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles strata on site for spec insp
|
BLD-Other | 10/6/2006 | 10/6/2006 | 10/6/2006 | P | PASS |
Tom Arcoraci
|
|
|
conf on hotel plans
|