FIRE-Final Inspection | 10/2/2007 | 10/2/2007 | 10/3/2007 | P | PASS |
Troy Cobbley
|
|
|
Life safety passed
|
BLD-Final | 10/2/2007 | 10/2/2007 | 10/2/2007 | P | PASS |
Jim Sly
|
|
|
Phone #: ###-#### Internet Inspection Request from: Dale Shuart OK for Perm Occ.
|
Code Occupancy Approval | 9/7/2007 | 9/7/2007 | 9/7/2007 | A | PASS |
Carol Montgomery
|
|
|
|
Code Occupancy Approval Temp | 9/5/2007 | 9/5/2007 | 9/5/2007 | A | FAIL |
Carol Montgomery
|
|
|
Made inspection of site on 9-4-2007. Still have a small amount of hydroseeding to do and the remainder of the landscaping (incl. undergrd. sprinkle system) at the sw corner of the project. There is a $9,400.00 Bond in place so I am signing off on temporary(s)
|
BLD-Final | 8/31/2007 | 9/4/2007 | 9/4/2007 | P | NR |
Jim Sly
|
|
|
Final for D wing. Phone #: ###-#### Internet Inspection Request from: Dale Shuart
|
BLD-Conference | 8/31/2007 | 9/4/2007 | 8/31/2007 | P | CANC |
Jim Sly
|
|
|
Final in D wing! Phone #: ###-#### Internet Inspection Request from: Dale Shuart Inspection cancelled from web by: Dale Shuart
|
BLD-Final | 8/31/2007 | 9/4/2007 | 8/31/2007 | P | CANC |
Jim Sly
|
|
|
Final in A and B wings. Phone #: ###-#### Internet Inspection Request from: Dale Shuart Inspection cancelled from web by: Dale Shuart
|
BLD-Conference | 8/24/2007 | 8/27/2007 | 8/27/2007 | A | PASS |
Jim Sly
|
|
|
Please inspect final attic insulation in D-wing. Thanks. Phone #: ###-#### Internet Inspection Request from: Dale Shuart
|
BLD-Other | 7/25/2007 | 7/31/2007 | 7/31/2007 | A | PASS |
Jim Sly
|
|
|
Please inspect D-wing T-bar ceiling 1st floor - see Dale first. Thanks Phone #: ###-#### Internet Inspection Request from: Dale Shuart
|
BLD-Wall cover | 7/2/2007 | 7/3/2007 | 7/3/2007 | A | PASS |
Jim Sly
|
|
|
Please inspect sheetrock nailing in D-wing 3rd floor completed units. Thanks. Phone #: ###-#### Internet Inspection Request from: Dale Shuart
|
BLD-Wall cover | 6/28/2007 | 6/28/2007 | 6/28/2007 | P | PASS |
Jim Sly
|
|
|
Please inspect 3rd floor D-wing sheetrock. Phone #: ###-#### Internet Inspection Request from: Dale Shuart
|
BLD-Energy code compliance | 6/25/2007 | 6/26/2007 | 6/26/2007 | A | PASS |
Jim Sly
|
|
|
Please inspect D-wing 3rd floor insulation. Phone #: ###-#### Internet Inspection Request from: Dale Shuart
|
BLD-Energy code compliance | 6/25/2007 | 6/25/2007 | 6/25/2007 | P | CANC |
Jim Sly
|
|
|
Please inspect insulation on 3rd floor of D-wing. Phone #: ###-#### Internet Inspection Request from: Dale Shuart
|
BLD-Wall cover | 6/13/2007 | 6/13/2007 | 6/13/2007 | P | PASS |
Jim Sly
|
|
|
Please inspect 1st layer sheetrock nailing on 3rd floor of D-wing. Thanks. Phone #: ###-#### Internet Inspection Request from: Dale Shuart
|
BLD-Conference | 6/12/2007 | 6/12/2007 | 6/12/2007 | P | PASS |
Jim Sly
|
|
|
Please inspect nailing in completed units on 2nd floor of D-wing. Thanks. Phone #: ###-#### Internet Inspection Request from: Dale Shuart
|
BLD-Energy code compliance | 6/8/2007 | 6/8/2007 | 6/8/2007 | P | PASS |
Jim Sly
|
|
|
Please inspect insulation on 2nd floor of D-wing. Thanks. Phone #: ###-#### Internet Inspection Request from: Dale Shuart
|
BLD-Wall cover | 6/6/2007 | 6/7/2007 | 6/7/2007 | P | PASS |
Jim Sly
|
|
|
Please inspect first layer lids and structural shear walls on 2nd floor of D-wing. Thanks. Phone #: ###-#### Internet Inspection Request from: Dale Shuart
|
BLD-Wall cover | 6/6/2007 | 6/7/2007 | 6/7/2007 | A | PASS |
Jim Sly
|
|
|
Please inspect completed units on 1st floor of D-wing. Thanks. Phone #: ###-#### Internet Inspection Request from: Dale Shuart Shear walls, flr/ceil. assemb, and all drywall OK in units..... 1st flr "D" wing.
|
BLD-Wall cover | 5/30/2007 | 5/31/2007 | 5/31/2007 | A | PASS |
Jim Sly
|
|
|
Please inspect 1st floor D-wing sheetrock: 1st layer lids and structural shear walls - see John Coe. Phone #: ###-#### Internet Inspection Request from: Dale Shuart
|
BLD-Wall cover | 5/29/2007 | 5/30/2007 | 5/31/2007 | A | CANC |
Jim Sly
|
|
|
Please inspect 1st floor D-wing sheetrock: 1st layer lids and structural shear walls - see John Coe. Phone #: ###-#### Internet Inspection Request from: Dale Shuart
|
BLD-Energy code compliance | 5/23/2007 | 5/24/2007 | 5/24/2007 | P | PASS |
Jim Sly
|
|
|
Please inspect 1st floor D-wing insulation. Thanks Phone #: ###-#### Internet Inspection Request from: Dale Shuart
|
BLD-Framing/Rough-in | 5/17/2007 | 5/18/2007 | 5/18/2007 | P | PASS |
Jim Sly
|
|
|
Please inspect 1st floor D-wing fire-caulking. Thanks! Phone #: ###-#### Internet Inspection Request from: Dale Shuart
|
BLD-Conference | 4/12/2007 | 4/12/2007 | 4/12/2007 | P | PASS |
Jim Sly
|
|
|
Please inspect shear nailing in D-wing (metal). Anytime today is fine. Tahnks. Phone #: ###-####
|
BLD-Framing/Rough-in | 4/11/2007 | 4/12/2007 | 4/12/2007 | A | PASS |
Jim Sly
|
|
|
Please inspect D-wing (metal) 3rd floor framing and trusses around 9 or 10 am if possible. See Brad w/ Lombac. Thanks! Phone #: ###-####
|
BLD-Framing/Rough-in | 2/21/2007 | 2/22/2007 | 2/22/2007 | A | PASS |
Jim Sly
|
|
|
Please inspect 2nd floor framing in D-wing. Thanks. Phone #: ###-####
|
BLD-Conference | 2/20/2007 | 2/21/2007 | 2/21/2007 | A | PART |
Jim Sly
|
|
|
Please inspect 2nd floor D-wing framing. Thanks. Phone #: ###-####
|
BLD-Framing/Rough-in | 2/8/2007 | 2/9/2007 | 2/9/2007 | P | PART |
Jim Sly
|
|
|
Please inspect D-wing steel stairs - Dale will walk inspection with you. Thanks. Phone #: ###-####
|
BLD-Framing/Rough-in | 2/6/2007 | 2/7/2007 | 2/7/2007 | P | PART |
Jim Sly
|
|
|
Please inspect walls and trusses at MDP Room in PM near D-wing. Thanks. Phone #: ###-#### OK
|
BLD-Framing/Rough-in | 2/5/2007 | 2/6/2007 | 2/6/2007 | P | PART |
Jim Sly
|
|
|
Please inspect pandeck screwing at metal D-wing. Thank you. Phone #: ###-#### OK
|
BLD-Footing | 1/12/2007 | 1/16/2007 | 1/16/2007 | A | PART |
Jim Sly
|
|
|
Please inspect footings for MDP room (near D-wing) as early as possible on Tuesday. Thanks! Phone #: ###-#### OK pend special insp MTI
|
BLD-Framing/Rough-in | 1/10/2007 | 1/10/2007 | 1/10/2007 | P | PASS |
Jim Sly
|
|
|
Please inspect rest of 1st floor D-wing (metal framed wing) in PM. Phone #: ###-####
|
BLD-Framing/Rough-in | 1/8/2007 | 1/10/2007 | 1/9/2007 | P | NH |
Jim Sly
|
|
|
Please inspect the rest of D-wing 1st floor framing (metal framed wing). Thank you. Phone #: ###-#### Could not find John at jobsite.
|
BLD-Concrete | 1/8/2007 | 1/8/2007 | 1/8/2007 | P | PASS |
Jim Sly
|
|
|
Please inspect wire mesh on 2nd floor D-wing pandeck. Thank you. Phone #: ###-####
|
BLD-Framing/Rough-in | 12/29/2006 | 1/2/2007 | 1/2/2007 | P | PASS |
Tony Young
|
|
|
Please inspect screwing at pandeck in the D-wing. Thanks and Happy New Year.; Phone #: ###-#### Internet Inspection Request from: Dale Shuart
|
BLD-Framing/Rough-in | 12/15/2006 | 12/15/2006 | 12/15/2006 | P | PART |
Jim Sly
|
|
|
Please inspect pandeck screwing at D-wing today. This morning would work too...sorry about late notice. Thanks Jim!; Phone #: ###-#### Internet Inspection Request from: Dale Shuart East 1/3 D wing pan deck fastening OK.
|
BLD-Framing/Rough-in | 12/5/2006 | 12/7/2006 | 12/7/2006 | P | PART |
Jim Sly
|
|
|
Please inspect screwing of 2nd floor pandeck at D-wing (metal framed wing). Thanks. ; Phone #: ###-#### Internet Inspection Request from: Dale Shuart OK
|
BLD-Framing/Rough-in | 11/10/2006 | 11/13/2006 | 11/13/2006 | A | PART |
Jim Sly
|
|
|
Please inspect framing on 1st floor of D-wing (metal framed) to L-line. ; Phone #: ###-#### Internet Inspection Request from: Dale Shuart
|
BLD-Other | 10/31/2006 | 11/1/2006 | 11/1/2006 | A | DONE |
Jim Sly
|
|
|
Please meet John Woods for consultation on D-wing (metal frame) in morning if possible). Thanks; Phone #: ###-#### Internet Inspection Request from: Dale Shuart
|
BLD-Foundation | 10/9/2006 | 10/11/2006 | 10/11/2006 | A | PART |
Jim Sly
|
|
|
Please inspect rebar at D-wing in AM. Thanks.; Phone #: ###-#### Internet Inspection Request from: Dale Shuart OK pending MTI special insp, tests and approals.
|
BLD-Footing | 9/20/2006 | 9/21/2006 | 9/21/2006 | A | PART |
Jim Sly
|
|
|
Please inspect D-wing elevator floor in morning. ; Phone #: ###-#### Internet Inspection Request from: Dale Shuart OK Pending MTI special insp, tests and approvals.
|
BLD-Footing | 9/14/2006 | 9/15/2006 | 9/15/2006 | P | PART |
Jim Sly
|
|
|
Please inspect footings for D-wing during PM.; Phone #: ###-#### Internet Inspection Request from: Dale Shuart OK Pending MTI special insp tests and approvals
|