Permit Information
Permit NumberBLD06-01831
StatusFinaled
Name COLLIER'S INTERNATIONAL
Site Address 755 W FRONT ST Unit: 200
Project NameMEULEMAN MOLLERUP LLP BODO 7
Customer Number 
ePlanReviewNo
Description
(RCE-8702 - COLLIERS INTERNATIONAL) (MEULEMAN MOLLERUP LLP - BODO BLDG #7 - 2ND STORY) This building is fire sprinklered for fire area and to allow the multitheater complex. To construct a 9,983 square foot office tenant space on the 2nd story of BoDo Building #7 (Northeast corner). Work is to include 2 restrooms accessible to the disabled, a shower room accessible to the disabled, interior nonbearing walls, interior doors, interior windows, suspended acoustical ceilings, suspended gypsum board ceilings, millwork, and interior finishes. The work is required to comply with the approved drawings, with the plan review report, and with all applicable codes. The fire sprinkler system is required to comply with NFPA 13 as regulated by the Fire Department. **CJW**
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
BLD-Final2/28/20072/28/20072/28/2007PPASS
DetailsDave Hannah
Rob; Phone #: ###-#### Internet Inspection Request from: Victoria Beall ok for perm occ
BLD-Final2/27/20072/28/20072/28/2007ACANC
DetailsDave Hannah
Rob; Phone #: ###-#### Internet Inspection Request from: Victoria Beall
Permanent Occupancy 2/28/20072/28/2007 DONE
Details
FIRE-Final Inspection1/10/20071/11/20071/11/2007APASS
DetailsForrest France
Required corrections have been verified for completion, fire life safety final inspection passed.
BLD-Final1/4/20071/5/20071/8/2007PPART
DetailsDave Hannah
Scheduled by a contractor via Hello! on 1/4/2007 at 10:29:00 AM. Contact: ###-####. ok for temp occ needs to fix ada shower and hl
oles in floor
FIRE-Final Inspection1/4/20071/5/20071/5/2007APART
DetailsForrest France
Agreed in conjunction with the structural inspector to allow temporary occupancy pending the replacement of four light fixtures with defective emergency ballasts. Corrections are to be made and verified for completion early next week as discussed.
FIRE-Final Inspection1/4/20071/5/20071/5/2007ACANC
DetailsDave Hannah
Scheduled by a contractor via Hello! on 1/4/2007 at 10:28:20 AM. Contact: ###-####. wrong inspector
BLD-Framing/Rough-in12/22/200612/22/200612/22/2006PPART
DetailsJim Storey
rich judy///ceiling grid inspection please; Phone #: ###-#### Internet Inspection Request from: Barbara Stitt floor firestopping not done/ pvc plm in return air plenm/needs spreader bars.hole in stair encloser. ok to start but leave access for reinsp.
BLD-Framing/Rough-in11/29/200611/30/200611/30/2006APASS
DetailsDave Hannah
Scheduled by a contractor via Hello! on 11/29/2006 at 5:57:22 PM. Contact: ###-####.ok to cover restroom plumbing wall
BLD-Framing/Rough-in11/28/200611/29/200611/29/2006PPART
DetailsDave Hannah
Scheduled by a contractor via Hello! on 11/28/2006 at 3:50:35 PM. Contact: ###-####.ok to cover all but restroom plumbing wall
BLD-Energy code compliance11/15/200611/16/200611/16/2006PNR
DetailsDave Hannah
Scheduled by a contractor via Hello! on 11/15/2006 at 4:47:01 PM. Contact: ###-####.
BLD-Energy code compliance11/14/200611/16/200611/15/2006ACANC
DetailsDave Hannah
Scheduled by a contractor via Hello! on 11/14/2006 at 4:15:51 PM. Contact: ###-####. Disp set to [CANC] by a contractor via Hello! on Nov 15 2006 4:51PM.
FIRE-Conference11/14/200611/15/200611/15/2006PPASS
DetailsTroy Cobbley
The contractor had a question about a pipe penatration through a rated wall
BLD-Framing/Rough-in11/14/200611/15/200611/15/2006APART
DetailsDave Hannah
Scheduled by a contractor via Hello! on 11/14/2006 at 4:13:44 PM. Contact: ###-####. ok to insulate ext walls
BLD-Conference6/27/20066/27/20066/28/2006PDONE
DetailsForrest France
Phone conversation with contractor regarding duct smoke detection requirements for HVAC shutdown in a proposed common plenum.
BLD-Conference6/27/20066/27/20066/27/2006APASS
DetailsDixie Fellows
per dixie..referred richard kartchner to sam rogers regarding outside fresh air not being ducted to r/a on all units..they are using the ceiling as a plenum and the units will all have duct detectors in the r/a's.