BLD-Final | 1/29/2007 | 1/30/2007 | 1/30/2007 | A | PASS |
Dave Hannah
|
|
|
matt; Phone #: ###-#### Internet Inspection Request from: Darla Downs ok for perm occ
|
Permanent Occupancy | | 1/30/2007 | 1/30/2007 | | DONE |
|
|
|
|
BLD-Final | 1/11/2007 | 1/12/2007 | 1/12/2007 | P | PART |
Dave Hannah
|
|
|
matt - fire life safety ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith ok for temp occ need to finish installing glassing and divider wall in conf rm
|
FIRE-Final Inspection | 1/12/2007 | 1/12/2007 | 1/12/2007 | P | PASS |
Forrest France
|
|
|
Verified necessary corrections, fire life safety finaled.
|
FIRE-Final Inspection | 1/11/2007 | 1/12/2007 | 1/12/2007 | A | FAIL |
Forrest France
|
|
|
Missing building address numbers at the front entrance, two exit signs at the training room are not installed as red lined on approved plans, one emergency light is missing in the confrence room, need max. occupant load signs in the training rooms per review notes.
|
BLD-Other | 1/10/2007 | 1/10/2007 | 1/10/2007 | P | PART |
Dave Hannah
|
|
|
jack Note: ceiling ins is possible after 2:00 pm; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles ok to cover
|
BLD-Other | 1/4/2007 | 1/4/2007 | 1/5/2007 | P | FAIL |
Dave Hannah
|
|
|
###-#### - jack Note: ceiling grid needs to patch fire proofing and add a wire to mec fixtures
|
FIRE-Sprinkler Rough-in | 12/29/2006 | 12/29/2006 | 12/29/2006 | P | PART |
Troy Cobbley
|
|
|
See approved plans for areas where piping is ok to cover. I found one pendant in front of the restrooms overspaced and four pendants overspaced off of the accordian door in the training room. See approved plans these locations.
|
BLD-Other | 12/20/2006 | 12/21/2006 | 12/21/2006 | A | PART |
Dave Hannah
|
|
|
Jack Note: sup ceiling insp; Phone #: ###-#### Internet Inspection Request from: Sherri Bennett ok to cover front area after all other trades ok
|
BLD-Framing/Rough-in | 11/29/2006 | 11/30/2006 | 11/30/2006 | A | PASS |
Dave Hannah
|
|
|
matt ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith ok to cover ext walls insulation ok fireproofing also ok
|
BLD-Framing/Rough-in | 11/22/2006 | 11/22/2006 | 11/24/2006 | P | PART |
Dave Hannah
|
|
|
loressa; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles ok to insulate ext wall ok to cover int walls
|
BLD-Framing/Rough-in | 11/21/2006 | 11/22/2006 | 11/22/2006 | A | CANC |
Dave Hannah
|
|
|
Scheduled by a contractor via Hello! on 11/21/2006 at 2:15:21 PM. Contact: ###-####.
|