Permit Information
Permit NumberBLD06-02615
StatusFinaled
Name CONGER-SAUCERMAN
Site Address 9288 W EMERALD ST
Project NameGE HARRIS LLC
Customer Number 
ePlanReviewNo
Description
CONGER/SAUCERMAN RCE # 2946 (T-MOBILE COMMUNICATIONS) This building is fire sprinklered for area increase. To construct a 9,307 square foot telephone exchange tenant space within an existing 20,634 square foot building. Work is to include 1-hr fire barrier walls around a battery room control area, interior nonbearing walls, interior doors, 2 new exterior doors, a single user shower room accessible to the disabled, suspended ceilings, and interior finishes. In addition, two existing restrooms will be upgraded to be accessible to the disabled. A 2,377 square foot equipment enclosure will be constructed next to this building. A generator with fuel tanks and condensers for cooling will be installed within the enclosure. The enclosure will be surrounded by a chain link fence and will be open to the sky. The work is required to comply with the approved drawings, with the plan review report, and with all applicable codes. The fire sprinkler system is required to comply with NFPA 13 as regulated by the Fire Department. **CJW**
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
BLD-Final5/22/20075/22/20075/22/2007PPASS
DetailsMike Jordan
rich; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles. Ok for perm occ. All issues resolved.
Permanent Occupancy 5/22/20075/22/2007 DONE
Details
FIRE-Final Inspection5/1/20075/1/20075/1/2007PPASS
DetailsTroy Cobbley
Life safety passed.
BLD-Final3/22/20073/23/20073/23/2007PPART
DetailsMike Jordan
rich ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith. Temp. occ. granted. Needs to post HC signs and finish installing grab bars in restrooms. Replace door hardware on janitors closet to lever type. All ceiling grid issues have been resolved and is ok to cover.
FIRE-Final Inspection3/23/20073/23/20073/23/2007PPART
DetailsTroy Cobbley
A temporary occupancy was given with dave hannimans permission until items as noted by mike timmermans inspection have been corrected for the fire alarm and suppression permits. Also the battery containment issues needs addressed.
BLD-Other3/21/20073/21/20073/21/2007PFAIL
DetailsMike Jordan
Rich Ceiling ; Phone #: ###-#### Internet Inspection Request from: Stacie Backus. Tile already in place. Noted upon further insp. that additional wires needed for diffusers, etc... Also needs rto remove wall angle used to attach runners and used approved connectors.
Code Occupancy Approval3/19/20073/19/20073/20/2007PPASS
DetailsCarol Montgomery
Meets compliance (insp. on 3-19-2007)
Code Occupancy Approval3/14/20073/16/20073/19/2007ACANC
DetailsCarol Montgomery
Rich called at approx. 4:00pm- NR
Code Occupancy Approval3/13/20073/13/20073/14/2007PCANC
DetailsCarol Montgomery
Called Rich. They have landscape in and fence posts up. Fence is not completed - so, they are not ready for inspection - schedule inspection for Friday (3-16-2007)
FIRE-Final Inspection2/22/20072/22/20072/22/2007PFAIL
DetailsTroy Cobbley
Inspection was not for a final but for a cover inspection on part of the sprinkler piping. The sprinkler piping in the areas outside of the pre-action system areas are ok to cover.
BLD-Framing/Rough-in2/9/20072/9/20072/9/2007PPASS
DetailsMike Jordan
rich; Phone #: ###-#### Internet Inspection Request from: Victoria Beall. On site to inspect truss penetration repair at 1hr fire barrier wall around battery room. All modifications were done in accordance with plans approved by G. Slane
BLD-Framing/Rough-in11/27/200611/28/200611/28/2006AFAIL
DetailsMike Jordan
richard; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles. Wood truss and wood beam penetrations not allowed at 1hr fire barrier wall. Architect to provide UL approved listed assembly for wood truss and wood beam penetrations or provide detail to plan review for approval for aequate protection.