Permanent Occupancy | | 1/9/2007 | 1/9/2007 | | DONE |
|
|
|
|
BLD-Final | 1/5/2007 | 1/5/2007 | 1/5/2007 | P | PART |
Jim Storey
|
|
|
paul - please call 1/2 hr prior to inspection ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith perm final ok pending mech gas pipping insp.
|
FIRE-Final Inspection | 1/4/2007 | 1/4/2007 | 1/4/2007 | P | PASS |
Forrest France
|
|
|
Required corrections have been made, fire life safety inspection passed.
|
BLD-Final | 12/29/2006 | 1/2/2007 | 1/2/2007 | A | NR |
Jim Storey
|
|
|
paul - please call 1/2 prior to inspection please ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith
|
FIRE-Final Inspection | 12/29/2006 | 12/29/2006 | 12/29/2006 | P | FAIL |
Forrest France
|
|
|
Missing emergency lighting as indicated on approved plans and per fire code review notes, the sample tube in the duct detector is incorrect.
|
BLD-Other | 12/8/2006 | 12/8/2006 | 12/8/2006 | P | PASS |
Jim Storey
|
|
|
paul - note: ceiling grid - please call 1/2 hr prior to inspection ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith ceilling ok
|
BLD-Framing/Rough-in | 11/7/2006 | 11/9/2006 | 11/9/2006 | P | PART |
Jim Storey
|
|
|
paul - please call 1/2 hr prior to inspection ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith framing ok pending remove ele from gyp colum/ verify stair wall above hard lid from south tennet side for fire stopping of vent pipe/ same with mech vent duct.
|