Permit Information
Permit NumberBLD06-02843
StatusFinaled
Name DATUM CONSTRUCTION MANAGEMENT INC
Site Address 8491 W ELISA ST
Project NameVIC PARK SMALL BLDG 'A'
Customer Number 
ePlanReviewNo
Description
(Datum Construction RCE-702) Vic Park Small Building A - To construct a new 5,350 square foot, one story, pre-engineered metal office and fabrication/warehouse building and related site improvements. The office area is 825 sq. ft. and the fabrication/warehouse area is 4,525 sq. ft.. After a tenant has been selected for this building, an MIS permit will be required to establish the Certificate of Occupancy. All construction per the approved plans and attached comment list. JCM
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
BLD-Final7/16/20077/17/20077/17/2007APASS
DetailsMike Jordan
Scheduled by a contractor via Hello! on 7/16/2007 at 4:47:38 PM. Contact: ###-####.
DOC - Permit Finaled7/17/20077/17/20077/17/2007PPASS
DetailsMike Jordan
All required signatyres on card. Letter of compliance issued.
Code Occupancy Approval7/13/20077/13/20077/13/2007PPASS
DetailsScott M.Brown
ALL IN AS REQUIRED FINAL SIGNED
FIRE-Final Inspection7/12/20077/13/20077/13/2007APASS
DetailsTroy Cobbley
life safety passed
BLD-Other6/19/20076/20/20076/20/2007PPART
DetailsMike Jordan
Scheduled by a contractor via Hello! on 6/19/2007 at 3:49:23 PM. Contact: ###-####. ceiling grid.
BLD-Energy code compliance6/4/20076/4/20076/4/2007APASS
DetailsMike Jordan
BLD-Framing/Rough-in6/1/20076/4/20076/4/2007APASS
DetailsMike Jordan
BLD-Framing/Rough-in5/31/20076/1/20076/1/2007PPART
DetailsMike Jordan
Scheduled by a contractor via Hello! on 5/31/2007 at 11:52:40 AM. Contact: ###-####. ok to one side.
BLD-Framing/Rough-in4/9/20074/10/20074/10/2007APART
DetailsMike Jordan
Scheduled by a contractor via Hello! on 4/9/2007 at 1:13:07 PM. Contact: ###-####.
pre-engineered bldg. Needs special insp. on bolting.
BLD-Foundation2/16/20072/16/20072/16/2007PFAIL
DetailsMike Jordan
###-#### jason. Perimeter stemwalls. Vert. reinforcement for pedestals not installed. Contractor to get RFI from structural engineer for depth on dowells and have special insp. for epoxy of missing verts. Also will need to install #4 ties at 6 inches on center as per approved plan.
BLD-Footing2/13/20072/14/20072/14/2007APART
DetailsMike Jordan
Scheduled by a contractor via Hello! on 2/13/2007 at 11:42:37 AM. Contact: ###-####. Perimeter footing. Noted clearance issues and rebar not tied sufficiently. Special insp. to verify compliance. Contractor is having surveyor double check elev.