Permit Information
Permit NumberBLD06-03378
StatusFinaled
Name DAVE EVANS CONSTRUCTION
Site Address 987 S ALLANTE PL
Project Name 
Customer Number 
ePlanReviewNo
Description
Keller Williams #6 - To construct a new 5,900 square foot, one story, wood framed office building and related site improvements. Two additional exit doors and wall and door separations at the center of the tenant space were used as an equivalent of the required rated corridor and two exterior exit doors. All construction per the approved plans and attached comment list. JCM
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
BLD-Final8/6/20078/7/20078/7/2007PPASS
DetailsMike Jordan
dave Phone #: 941-274. Ok for perm occ.
FIRE-Final Inspection8/6/20078/7/20078/7/2007APASS
DetailsForrest France
Items on previous c/n notice verified for completion, life safety final passed.
FIRE-Final Inspection8/5/20078/6/20078/7/2007PFAIL
DetailsTroy Cobbley
The keyed locks on the north and south exit doors need to be removed.
FIRE-Final Inspection8/2/20078/3/20078/6/2007PFAIL
DetailsTroy Cobbley
The key locks need to be removed from the north and south exits
BLD-Final8/1/20078/2/20078/2/2007PNR
DetailsMike Jordan
Dave phone : ###-#### . Fire failed. Needs public works.
FIRE-Final Inspection7/30/20078/2/20078/2/2007AFAIL
DetailsTroy Cobbley
Access controlled egress doors are in the process of being installed and will need to be tested when ready. I called jim schmeer about ASI installing this system possibley without permits.
BLD-Final7/26/20078/1/20078/1/2007PCANC
DetailsMike Jordan
Scheduled by a contractor via Hello! on 7/26/2007 at 5:51:30 PM. Contact: ###-####. Inspection cancelled from web by: Patricia Smith
FIRE-Final Inspection7/27/20077/30/20077/30/2007PCANC
DetailsTroy Cobbley
zack - fire life safety Phone #: ###-#### Inspection cancelled from web by: Victoria Apatang
FIRE-Final Inspection7/26/20077/27/20077/27/2007AFAIL
DetailsTroy Cobbley
The south and the east exit discharge lights did not work. The north and south exit doors need approved hardware and the deadbolts removed. Per the plans there are three hvac units that require duct smoke detectors. I did not see remote annunciators as required. These duct detectors, if even installed, will need to be tested.
Code Occupancy Approval  7/27/2007 PASS
BLD-Energy code compliance4/19/20074/20/20074/20/2007APASS
DetailsTony Young
Zach; Phone #: ###-#### Internet Inspection Request from: Stacie Backus
BLD-Framing/Rough-in4/16/20074/17/20074/17/2007PPASS
DetailsMike Jordan
zack; Phone #: ###-#### Internet Inspection Request from: Patricia Smith. Needs to seal holes in draft stops. ok to insul.
BLD-Other3/9/20073/12/20073/12/2007PPASS
DetailsMike Jordan
Ben Sheer Nail; Phone #: ###-#### Internet Inspection Request from: Stacie Backus. exterior and roof shear nailing ok. Need approved plans for exit corridors.
BLD-Footing1/29/20071/29/20071/29/2007PPASS
DetailsMike Jordan
STEVE; Phone #: ###-#### Internet Inspection Request from: Darla Downs
BLD-Footing1/25/20071/26/20071/26/2007APASS
DetailsJim Storey
steve; Phone #: ###-#### Internet Inspection Request from: Victoria Beall