Permit Information
Permit NumberBLD06-03595
StatusExpired
Name DAVES CONSTRUCTION
Site Address 2036 N COLE RD
Project Name 
Customer Number 
ePlanReviewNo
Description
(DR NEWCOMBE OFFICE BLDG) 5/31/07 PLAN MODIFICATION. TO REDUCE THE EXTERIOR SCOPE OF WORK FOR ACCESSIBILITY UPGRADES BY LEAVING THE EXISTING MAIN ENTRY LANDING AND SIDEWALK AS IS AND ELIMINATING THE ACCESSIBLE RAMP AND ROUTE FROM THE PUBLIC SIDEWALK TO THE EXISTING BUILDING SIDEWALK. THE NEW ACCESSIBLE WORK WITHIN THE EXISTING OFFICE BUILDING AND THE NEW SOUTH END ACCESSIBLE ROUTE MEET OR EXCEED THE 20% UPGRADE REQUIRED UNDER SECTION 3409 IBC. 6/29/07 PLAN MODIFICATION OF NORTH HALF OF DR. OFFICE. REMAINDER OF PROJECT AND ATTACHED PLAN REVIEW COMMENTS OF ALL AGENCIES REMAIN THE SAME. To remodel the interior of the 2,883 sq.ft. doctor's office and modify exterior with sidewalks, ramps, etc. per approved plans and CZC06-00170. Work includes selective demolition; construction of three fully accessible restrooms (staff/his/hers), drinking fountain; new reception/waiting area, office, exam & work areas; upgrade electrical, plumbing and mechanical as per plans. Existing items not modified can remain per original codes. All new work to comply with current codes. Door hardware shall comply with Sec. 1008.1.8, 2003 IBC. New occupancy sensors for lighting provided. drs
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
BLD-Aging Inspection6/12/20086/12/20086/12/2008 CANC
DetailsTom Arcoraci
DOC - Permit Expired6/12/20086/12/20086/12/2008APASS
DetailsTom Arcoraci
BLD-Aging Inspection2/25/20082/25/20082/25/2008 DONE
DetailsTom Arcoraci
exp 6-08
BLD-Final12/3/200712/3/200712/3/2007PPASS
DetailsJim Sly
Mike Phone #: ###-####
OK for Perm Occ.
FIRE-Final Inspection11/30/200711/30/200711/30/2007PPASS
DetailsTroy Cobbley
life safety passed.
BLD-Final11/29/200711/30/200711/30/2007ANR
DetailsMike Jordan
dave - please call 20 min prior to inspection Phone #: ###-####. Needs life/safety first to final out north portion.
BLD-Aging Inspection10/4/200710/4/200710/4/2007 PASS
DetailsTom Arcoraci
BLD-Framing/Rough-in7/31/20078/1/20078/1/2007APASS
DetailsTom Arcoraci
Dave ###-####
FIRE-Final Inspection5/25/20075/29/20075/29/2007APART
DetailsTroy Cobbley
The south phase of the project is ok to occupy. The north area still needs to be remodeled and then inspected.
FIRE-Final Inspection5/25/20075/25/20075/25/2007PDEFR
DetailsForrest France
Inspection to be rescheduled.
FIRE-Final Inspection5/22/20075/22/20075/22/2007PFAIL
DetailsTroy Cobbley
Emergency ligthing is required in all paths of egress as well as exit discharge lighting. The thumbturn needs to be removed from the south exit. Approved hardware needs to be provided on the west exit. The landings are incorrect but being worked on per the contractor. This inspection was only for the south half of the project.
BLD-Final5/17/20075/17/20075/17/2007PPART
DetailsDave Hannah
Dave - pls call 30 min prior - for 1/2 building; Phone #: ###-#### Internet Inspection Request from: Victoria Beall ok to move to south half after fire life saftey oks
BLD-Framing/Rough-in2/16/20072/20/20072/20/2007APASS
DetailsJim Sly
davd - pls call 30 min prior to inspect; Phone #: ###-#### Internet Inspection Request from: Victoria
Frame and Energy OK SOUTH 1/2 f