DOC - Permit Expired | 4/19/2011 | 4/19/2011 | 4/19/2011 | P | PASS |
Dave Hannah
|
|
|
|
BLD-Aging Inspection | 4/18/2011 | 4/18/2011 | 4/19/2011 | | PASS |
Dave Hannah
|
|
|
|
BLD-Aging Inspection | 1/7/2011 | 1/7/2011 | 1/13/2011 | | PASS |
Dave Hannah
|
|
|
|
FIRE-Final Inspection | 2/12/2008 | 2/12/2008 | 2/15/2008 | P | PASS |
Forrest France
|
|
|
Fire life safety passed.
|
BLD-Final | 2/12/2008 | 2/12/2008 | 2/13/2008 | P | PART |
Dave Hannah
|
|
|
walt Phone #: ###-#### ok to occ. two offices on east side of project still working on rest of project
|
FIRE-Final Inspection | 2/7/2008 | 2/8/2008 | 2/8/2008 | A | PART |
Forrest France
|
|
|
Missing one exit sign at the north exit stairway door- see approved plans for annotations regarding location, also need to final aging fire alarm pemit for elevator recall prior to final occupancy approval.
|
FIRE-Final Inspection | 2/7/2008 | 2/7/2008 | 2/7/2008 | A | PART |
Kenneth R Roule
|
|
|
When testing fire alarm, permit# FIR08-00046. Found that doors to elevator lobbys when released upon a fire alarm did not close correctly. Also found an aging permit #FIR03-00788 has not been finaled. This permit is for elevator recall, in duct detection with dampers and heat detection in elevator room. This building permit can't be finaled until FIR03-00788 is finaled do to life safety.Also found many sprinkler heads on 2nd floor covered with tape due to painting.Tape will also have to be removed before final inspection.
|
BLD-Framing/Rough-in | 1/2/2008 | 1/2/2008 | 1/2/2008 | P | PART |
Dave Hannah
|
|
|
walt Phone #: ###-####ok to cover walls on to west side of hall
|
FIRE-Final Inspection | 12/17/2007 | 12/18/2007 | 12/18/2007 | A | FAIL |
Forrest France
|
|
|
A fire alarm permit will be required for alteration and extension of the existing building FA system to include notification within this tenant remodel-see fire code review comments and notes attatched to the approved plan set, also noted the scope of work as indicated is not complete- missing walls, doors and finishes at several locations particularly on the west side of the corridor.
|
BLD-Final | 12/11/2007 | 12/12/2007 | 12/12/2007 | A | FAIL |
Dave Hannah
|
|
|
Walt; Phone #: ###-#### Internet Inspection Request from: Cathy Weisshaupt needs fire inspections and install glass
|
BLD-Framing/Rough-in | 11/15/2007 | 11/15/2007 | 11/16/2007 | P | PART |
Dave Hannah
|
|
|
walt Phone #: ###-#### ok to cover walls on east side of project
|
BLD-Framing/Rough-in | 11/14/2007 | 11/15/2007 | 11/15/2007 | A | FAIL |
Dave Hannah
|
|
|
walt Phone #: ###-#### no city set of plans on site
|
BLD-Aging Inspection | 9/6/2007 | 9/6/2007 | 9/10/2007 | | PASS |
Dave Hannah
|
|
|
|