BLD-Final | 6/28/2007 | 6/29/2007 | 6/29/2007 | A | PASS |
Mike Jordan
|
|
|
ok for perm occ.
|
FIRE-Final Inspection | 6/27/2007 | 6/28/2007 | 6/28/2007 | P | PASS |
Troy Cobbley
|
|
|
life safety passed
|
Extend Permit 180 days | 6/28/2007 | 6/29/2007 | 6/28/2007 | A | CANC |
Mike Jordan
|
|
|
|
BLD-Final | 6/28/2007 | 6/28/2007 | 6/28/2007 | P | CANC |
Mike Jordan
|
|
|
|
BLD-Final | 6/27/2007 | 6/29/2007 | 6/28/2007 | A | CANC |
Mike Jordan
|
|
|
mor Phone #: ###-####
|
BLD-Final | 6/25/2007 | 6/26/2007 | 6/26/2007 | P | NR |
Jim Sly
|
|
|
Dan; Phone #: ###-#### Internet Inspection Request from: Cathy Weisshaupt Need Fire final.
|
FIRE-Final Inspection | 6/22/2007 | 6/25/2007 | 6/25/2007 | A | FAIL |
Forrest France
|
|
|
Need to repair one emergency light at the main lobby, remove manual thumbturn at the office door, post the provided 2A10BC fire extinguisher on the wall as discussed, need to final the project related fire alarm permit prior to life safety final, noted slider doors at three private dining rooms may not meet hardware accessibility requirements as installed.
|
BLD-Final | 6/22/2007 | 6/25/2007 | 6/25/2007 | P | NR |
Jim Sly
|
|
|
mor Phone #: ###-#### Need Fire final approval.
|
BLD-Foundation | 6/5/2007 | 6/5/2007 | 6/5/2007 | P | DONE |
Mike Jordan
|
|
|
mor; Phone #: ###-#### Internet Inspection Request from: Victoria Apatang. CONFERANCE
|
FIRE-Final Inspection | 5/16/2007 | 5/17/2007 | 5/17/2007 | A | FAIL |
Troy Cobbley
|
|
|
This project was not ready for inspection but I went over some of the required items with the owner. Fire sprinkler heads are overspaced. Fire extinguishers need to be installed. There are no appliances under the kitchen hood yet so the suppression system needs recertified and tested. Door hardware is not installed. Exit signs and emergency lights will need to be tested.
|
BLD-Framing/Rough-in | 5/11/2007 | 5/14/2007 | 5/14/2007 | A | PASS |
Mike Jordan
|
|
|
Mor ###-####. Framing for tatami rooms, and fountain bases. Also verified with contractor that one leaf of sliding doors must provide 32" clear width. Also went over ada requirements with owners.
|