Permit Information
Permit NumberBLD07-00908
StatusFinaled
Name COMMUNITY CONTRACTING
Site Address 1020 W MAIN ST Unit: 100
Project NameALASKA BLDG1ST FLOOR TI
Customer Number 
ePlanReviewNo
Description
**(Vanilla Finish)** (Suite #100 First floor)** To remodel a 2810 sq ft tenant area located on the first floor and mezzanine for future tenant, (1st floor 1596 sq ft) (mezzanine 1243 sq ft) per approved plans . NO OCCUPANCY ALLOWED UNDER THIS PERMIT. Work to inlcude, construction of a 18 lf of nonbearing partition to create two office areas and a separate tenant space that will be permitted under BLD07-00909. Miscellaneous related finishes. This building is fully fire sprinklered ANY ALTERATIONS TO THE SPRINKLER SYSTEM WILL REQUIRE A SEPARATE PERMIT, and shall be maintain per NFPA #13 as regulated by the fire department. RmH
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
BLD-Final9/26/20079/27/20079/27/2007APASS
DetailsDave Hannah
jim Phone #: ###-####
DOC - Permit Finaled9/27/20079/27/20079/27/2007PPASS
DetailsDave Hannah
FIRE-Final Inspection9/26/20079/26/20079/26/2007PPASS
DetailsForrest France
Items on correction notice verified for compliance, fire life safety inspection passed, contractor to provide "door to remain unlocked while building is occupied" signage at the main entry/exit prior to structural final as discussed, PFE's to be installed at tenant occupancy.
BLD-Conference9/19/20079/19/20079/20/2007PPASS
DetailsDave Hannah
BLD-Final9/14/20079/17/20079/17/2007PFAIL
DetailsDave Hannah
jim Phone #: ###-#### needs fire signoffs
FIRE-Final Inspection9/14/20079/17/20079/17/2007AFAIL
DetailsForrest France
Missing approved door hardware at the second floor stairway exit and office doors, need to install two exit signs at the 2nd floor as red-lined per plan review, missing a fire sprinkler head in a utility closet on the second floor, remove the manual thumbturn at the main entry/exit door, provide lever hardware at all locations as indicated on plans, no fire sprinkler protection has been provided for the mech/utility room on the first floor, need to final fire sprinkler permit prior to life safety final.
BLD-Framing/Rough-in7/27/20077/27/20077/27/2007PPASS
DetailsDave Hannah
jim Phone #: ###-####
BLD-Conference5/18/20075/21/20075/21/2007APART
DetailsDave Hannah
jim campbell; Phone #: ###-#### Internet Inspection Request from: Delphine Kavanaugh went over project and ada ramp