BLD-Final | 8/23/2007 | 8/24/2007 | 8/24/2007 | P | PASS |
Jim Sly
|
|
|
jim Phone #: 941-451 Verified affidavit from MTI and final letter from Engineer. C/C issued
|
DOC - Permit Finaled | 8/24/2007 | 8/24/2007 | 8/24/2007 | P | PASS |
Jim Sly
|
|
|
|
BLD-Final | 8/23/2007 | 8/23/2007 | 8/23/2007 | P | NR |
Jim Sly
|
|
|
JIM Phone #: ###-#### Need 2 HVAC permits finaled.
|
BLD-Final | 8/21/2007 | 8/22/2007 | 8/22/2007 | P | PART |
Tony Young
|
|
|
jim Phone #: ###-#### temp occ ok,, need trades complete finals,, letter of approval for special inspections,, and any letter of approvals from architect
|
FIRE-Final Inspection | 8/21/2007 | 8/22/2007 | 8/22/2007 | A | PASS |
Forrest France
|
|
|
Required corrections have been completed, fire life safety passed inspection.
|
FIRE-Final Inspection | 8/20/2007 | 8/21/2007 | 8/21/2007 | A | FAIL |
Forrest France
|
|
|
Missing required exit signs as indicated on approved plan set for the second floor level, also need to install one EM light and repair one existing EM light as annotated, remainder of life safety is acceptable.
|
BLD-Framing/Rough-in | 8/14/2007 | 8/14/2007 | 8/14/2007 | P | PASS |
Tony Young
|
|
|
Ceiling grid; Jim; Phone #: ###-#### Internet Inspection Request from: Hattie James all ceiling grid ok
|
FIRE-Conference | 8/7/2007 | 8/8/2007 | 8/8/2007 | A | DONE |
Forrest France
|
|
|
On site visit to discuss fire code review notes and project related fire life safety issues including door hardware, exit signs/EM lighting, sprinkler coverage, fire alarm work, etc.
|
BLD-Other | 8/2/2007 | 8/3/2007 | 8/6/2007 | P | NR |
Dave Hannah
|
|
|
jim Note: ceiling grid Late as possible Phone #: ###-####
|
BLD-Framing/Rough-in | 8/1/2007 | 8/1/2007 | 8/1/2007 | P | PASS |
Tony Young
|
|
|
jim; Phone #: ###-#### Internet Inspection Request from: Victoria Apatang stair tower drop ceiling ok
|
BLD-Framing/Rough-in | 7/27/2007 | 7/30/2007 | 7/30/2007 | A | PART |
Tony Young
|
|
|
Jim,, stair tower; Phone #: ###-#### stair tower frame ok,, pending ele, r/in one area
|
BLD-Framing/Rough-in | 7/26/2007 | 7/27/2007 | 7/27/2007 | A | NR |
Tony Young
|
|
|
jim Phone #: ###-#### need u l listings,,
|
BLD-Framing/Rough-in | 7/19/2007 | 7/20/2007 | 7/20/2007 | P | PART |
Tony Young
|
|
|
jim - sheet rock in basement; Phone #: ###-#### Internet Inspection Request from: Victoria Apatang rock under beam ok
|
BLD-Other | 7/18/2007 | 7/18/2007 | 7/18/2007 | P | PART |
Tony Young
|
|
|
jim Phone #: ###-#### masonary window infill ok
|
BLD-Other | 7/17/2007 | 7/17/2007 | 7/17/2007 | P | PART |
Tony Young
|
|
|
jim - covering ceiling and fire taping Phone #: ###-#### all 4 ft areas that had been removed for seismic ties are ok now,, back to 1hr via 5/8 X sheetrock and sealed up,,
|
FIRE-Conference | 7/12/2007 | 7/12/2007 | 7/13/2007 | P | DONE |
Forrest France
|
|
|
On site visit, discussed repair of existing emergency lighting at the stairways, project schedule, related fire sprinkler and alarm permits.
|
BLD-Conference | 7/12/2007 | 7/12/2007 | 7/13/2007 | A | PART |
Tony Young
|
|
|
Jim; Phone #: ###-#### stair beam ok w/ wrapping w/ 5/8" to make 1hr assbly,, also 4' around classrooms ok replacing lath and plaster w/ 5/8" and seal to the you can w/ firecaulk,, sprinkler system is in portions of area above and below drop ceilings
|
BLD-Framing/Rough-in | 7/13/2007 | 7/13/2007 | 7/13/2007 | P | PART |
Tony Young
|
|
|
jim NOte: 2nd floor Phone #: ###-#### ok to cover hallway areas,,
|
BLD-Framing/Rough-in | 7/12/2007 | 7/12/2007 | 7/13/2007 | P | CANC |
Tony Young
|
|
|
Jim; Phone #: ###-####
|
BLD-Conference | 7/11/2007 | 7/11/2007 | 7/12/2007 | P | PASS |
Tony Young
|
|
|
JIM Phone #: ###-#### RFI# wrap of steel beam ok
|
BLD-Framing/Rough-in | 7/6/2007 | 7/9/2007 | 7/9/2007 | P | PART |
Tony Young
|
|
|
jim; Phone #: ###-#### Internet Inspection Request from: Victoria Apatang 3rd floor walls as noted on plans,, pendind elec r/in on some areas
|
BLD-Footing | 6/29/2007 | 7/2/2007 | 7/2/2007 | A | PASS |
Tony Young
|
|
|
Jim; Phone #: ###-#### stair ftg ok,, also all seismic ties in place
|
BLD-Footing | 6/28/2007 | 6/29/2007 | 7/2/2007 | A | PASS |
Tony Young
|
|
|
jim Note: rebar - if possible mid morning - concrete order about 11:00 Phone #: ###-####
|
BLD-Framing/Rough-in | 6/27/2007 | 6/28/2007 | 6/28/2007 | A | PART |
Tony Young
|
|
|
jim Phone #: ###-#### remainder of seismic straps
|
BLD-Framing/Rough-in | 6/25/2007 | 6/26/2007 | 6/26/2007 | P | PART |
Tony Young
|
|
|
jim Phone #: ###-#### 1st floor and ceiling seismic strapping,, see inspection sheet for room #s
|
BLD-Other | 6/15/2007 | 6/22/2007 | 6/22/2007 | A | PASS |
Tom Arcoraci
|
|
|
jim - seismic bracing; Phone #: ###-#### Internet Inspection Request from: Victoria Apatang 3rd floor 333 334 336 337 rms ok wip
|
BLD-Other | 6/15/2007 | 6/21/2007 | 6/21/2007 | A | PART |
Jim Sly
|
|
|
jim - seismic bracing; Phone #: ###-#### Internet Inspection Request from: Victoria Apatang Floor infill framing (old stairway) 2nd to 3rd floor......OK
|
BLD-Other | 6/15/2007 | 6/20/2007 | 6/20/2007 | A | CANC |
Jim Storey
|
|
|
jim - seismic bracing; Phone #: ###-#### Internet Inspection Request from: Victoria Apatang
|
BLD-Other | 6/15/2007 | 6/19/2007 | 6/19/2007 | A | CANC |
Tony Young
|
|
|
jim - seismic bracing; Phone #: ###-#### Internet Inspection Request from: Victoria Apatang
|
BLD-Other | 6/15/2007 | 6/18/2007 | 6/18/2007 | A | PART |
Dave Hannah
|
|
|
jim - seismic bracing; Phone #: ###-#### Internet Inspection Request from: Victoria Apatang third floor seismic straping ok to cover
|