DOC - Permit Finaled | 8/29/2008 | 8/29/2008 | 8/29/2008 | P | PASS |
Mike Jordan
|
|
|
|
BLD-Final | 8/29/2008 | 8/29/2008 | 8/29/2008 | P | PASS |
Mike Jordan
|
|
|
Matt Phone #: ###-####
|
FIRE-Final Inspection | 8/27/2008 | 8/28/2008 | 8/28/2008 | A | PASS |
Troy Cobbley
|
|
|
fire life safety passed
|
FIRE-Final Inspection | 8/22/2008 | 8/22/2008 | 8/22/2008 | P | PART |
Troy Cobbley
|
|
|
The insulation in tenant space 10480 is complete
|
FIRE-Final Inspection | 8/20/2008 | 8/21/2008 | 8/21/2008 | A | FAIL |
Troy Cobbley
|
|
|
This inspection was for the tenant at 10480. The insulation has not been adequately secured to the deck and is blocking the upright sprinkler head coverage and is laying on the sprinkler piping.
|
FIRE-Final Inspection | 8/11/2008 | 8/11/2008 | 8/11/2008 | P | PART |
Troy Cobbley
|
|
|
The piping in American Family Insurance, 10494, is ok to cover.
|
FIRE-Final Inspection | 6/13/2008 | 6/16/2008 | 6/16/2008 | A | CANC |
Troy Cobbley
|
|
|
Matt- fire life saftey Phone #: ###-####
|
FIRE-Final Inspection | 5/19/2008 | 5/20/2008 | 5/20/2008 | A | PART |
Troy Cobbley
|
|
|
The insulation in tenant addresses 10442 and 10436 has been installed and can be covered.
|
FIRE-Final Inspection | 5/15/2008 | 5/15/2008 | 5/15/2008 | P | PART |
Troy Cobbley
|
|
|
The insulation in tenant 10436 has been completed and can be covered.
|
FIRE-Final Inspection | 3/11/2008 | 3/11/2008 | 3/11/2008 | P | PART |
Troy Cobbley
|
|
|
The insulation at tenant space 10370 is passed.
|
FIRE-Final Inspection | 2/13/2008 | 2/14/2008 | 2/14/2008 | A | PART |
Troy Cobbley
|
|
|
The insulation in tenant address 10354 is passed.
|
FIRE-Final Inspection | 2/11/2008 | 2/12/2008 | 2/12/2008 | A | PART |
Troy Cobbley
|
|
|
The insulation at address 10476 is complete and can be covered.
|
FIRE-Final Inspection | 1/29/2008 | 1/29/2008 | 1/29/2008 | P | PART |
Troy Cobbley
|
|
|
The insulation at 10346 and 10352 has passed inspection.
|
FIRE-Final Inspection | 9/27/2007 | 9/27/2007 | 9/28/2007 | P | PASS |
Troy Cobbley
|
|
|
The insulation backing in tenant space 10390 has been completed
|
FIRE-Final Inspection | 8/30/2007 | 8/31/2007 | 8/31/2007 | A | PART |
Troy Cobbley
|
|
|
Tenant space 10464 is ok to cover. The second tenant space did not have all of the insulation backing held to the roof deck as agreed.
|
FIRE-Final Inspection | 8/7/2007 | 8/7/2007 | 8/8/2007 | P | PART |
Troy Cobbley
|
|
|
The new insulation backing has been installed in tenant spaces 10448, 10374 and 10366 and appears ok.
|
FIRE-Final Inspection | 6/28/2007 | 6/28/2007 | 6/29/2007 | P | PART |
Troy Cobbley
|
|
|
The insulation backing in the vacant tenant space next to the health food store has been installed and inspected.
|
FIRE-Final Inspection | 6/5/2007 | 6/6/2007 | 6/6/2007 | A | PART |
Troy Cobbley
|
|
|
Todays inspection was only for the 10488 address. Insulation backing appeared to be mounted ok.
|
FIRE-Final Inspection | 5/31/2007 | 6/1/2007 | 6/1/2007 | A | FAIL |
Troy Cobbley
|
|
|
The new insulation backing is laying on the upright sprinklers deflectors in many location. Code requires 1" clearance.
|