Permit Information
Permit NumberBLD07-01201
StatusFinaled
Name SELECT COMMERCIAL
Site Address 10436 W OVERLAND RD
Project NameFIVE MILE PLAZA
Customer Number 
ePlanReviewNo
Description
(RCE #2439 RA SCHULTZ & CO)(FIVE MILE PLAZA) To address last remaining work required under an Upgrade Agreement under BLD01-02612. The work will include addressing existing exposed noncompliant foil and paper backing on roof insulation in certain tenant spaces throughout the shopping center by perforating existing and installing a new scrim (FSK-25) with a flame spread index of not more than 25 and a smoke developed index of not more than 450 and to install additional support wires under insulation in some tenant spaces throughout the shopping center to eliminate sagging and obstruction of some fire sprinkler heads. See plan for exact work required in each tenant space. No work required in the Type III-B Albertson's building. This is a Scope of Work Permit. A Letter of Completion is to be issued when done. NOTE: The shopping center is fully fire sprinklered for area increase for each building area between fire walls. JCB
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
DOC - Permit Finaled8/29/20088/29/20088/29/2008PPASS
DetailsMike Jordan
BLD-Final8/29/20088/29/20088/29/2008PPASS
DetailsMike Jordan
Matt Phone #: ###-####
FIRE-Final Inspection8/27/20088/28/20088/28/2008APASS
DetailsTroy Cobbley
fire life safety passed
FIRE-Final Inspection8/22/20088/22/20088/22/2008PPART
DetailsTroy Cobbley
The insulation in tenant space 10480 is complete
FIRE-Final Inspection8/20/20088/21/20088/21/2008AFAIL
DetailsTroy Cobbley
This inspection was for the tenant at 10480. The insulation has not been adequately secured to the deck and is blocking the upright sprinkler head coverage and is laying on the sprinkler piping.
FIRE-Final Inspection8/11/20088/11/20088/11/2008PPART
DetailsTroy Cobbley
The piping in American Family Insurance, 10494, is ok to cover.
FIRE-Final Inspection6/13/20086/16/20086/16/2008ACANC
DetailsTroy Cobbley
Matt- fire life saftey Phone #: ###-####
FIRE-Final Inspection5/19/20085/20/20085/20/2008APART
DetailsTroy Cobbley
The insulation in tenant addresses 10442 and 10436 has been installed and can be covered.
FIRE-Final Inspection5/15/20085/15/20085/15/2008PPART
DetailsTroy Cobbley
The insulation in tenant 10436 has been completed and can be covered.
FIRE-Final Inspection3/11/20083/11/20083/11/2008PPART
DetailsTroy Cobbley
The insulation at tenant space 10370 is passed.
FIRE-Final Inspection2/13/20082/14/20082/14/2008APART
DetailsTroy Cobbley
The insulation in tenant address 10354 is passed.
FIRE-Final Inspection2/11/20082/12/20082/12/2008APART
DetailsTroy Cobbley
The insulation at address 10476 is complete and can be covered.
FIRE-Final Inspection1/29/20081/29/20081/29/2008PPART
DetailsTroy Cobbley
The insulation at 10346 and 10352 has passed inspection.
FIRE-Final Inspection9/27/20079/27/20079/28/2007PPASS
DetailsTroy Cobbley
The insulation backing in tenant space 10390 has been completed
FIRE-Final Inspection8/30/20078/31/20078/31/2007APART
DetailsTroy Cobbley
Tenant space 10464 is ok to cover. The second tenant space did not have all of the insulation backing held to the roof deck as agreed.
FIRE-Final Inspection8/7/20078/7/20078/8/2007PPART
DetailsTroy Cobbley
The new insulation backing has been installed in tenant spaces 10448, 10374 and 10366 and appears ok.
FIRE-Final Inspection6/28/20076/28/20076/29/2007PPART
DetailsTroy Cobbley
The insulation backing in the vacant tenant space next to the health food store has been installed and inspected.
FIRE-Final Inspection6/5/20076/6/20076/6/2007APART
DetailsTroy Cobbley
Todays inspection was only for the 10488 address. Insulation backing appeared to be mounted ok.
FIRE-Final Inspection5/31/20076/1/20076/1/2007AFAIL
DetailsTroy Cobbley
The new insulation backing is laying on the upright sprinklers deflectors in many location. Code requires 1" clearance.