BLD-Final | 10/29/2007 | 10/30/2007 | 10/30/2007 | P | PASS |
Mike Jordan
|
|
|
Scheduled by a contractor via Hello! on 10/29/2007 at 1:56:11 PM. Contact: ###-####. ok for perm occ.
|
FIRE-Final Inspection | 10/29/2007 | 10/30/2007 | 10/30/2007 | A | PASS |
Troy Cobbley
|
|
|
Life safety passed.
|
FIRE-Final Inspection | 10/29/2007 | 10/29/2007 | 10/29/2007 | A | FAIL |
Troy Cobbley
|
|
|
Provide exit discharge lighting as discussed.
|
BLD-Conference | 10/19/2007 | 10/22/2007 | 10/22/2007 | A | PASS |
Mike Jordan
|
|
|
Scheduled by a contractor via Hello! on 10/19/2007 at 5:25:58 PM. Contact: ###-####. Verified installation of remaining fire stop and collars on 2hr fire barrier wall.
|
BLD-Other | 10/11/2007 | 10/12/2007 | 10/12/2007 | A | PASS |
Jim Sly
|
|
|
Scheduled by a contractor via Hello! on 10/11/2007 at 12:47:15 PM. Contact: ###-####. Grid OK.
|
BLD-Conference | 9/17/2007 | 9/17/2007 | 9/17/2007 | P | PASS |
Mike Jordan
|
|
|
Scheduled by a contractor via Hello! on 9/17/2007 at 7:58:04 AM. Contact: ###-####. Reviewed UL tech data and installation of firestop material at 2hr fire barrier wall.
|
BLD-Framing/Rough-in | 9/4/2007 | 9/5/2007 | 9/5/2007 | A | PASS |
Mike Jordan
|
|
|
Scheduled by a contractor via Hello! on 9/4/2007 at 9:29:59 AM. Contact: ###-####. ok for 2nd layer of rock on 2hr fire barrier wall.
|
BLD-Framing/Rough-in | 8/31/2007 | 9/4/2007 | 9/4/2007 | A | PART |
Mike Jordan
|
|
|
Scheduled by a contractor via Hello! on 8/31/2007 at 10:49:15 AM. Contact: ###-####. Verified putty pads, 1st. layer of rock, insul on 2hr fire barrier wall.
|
BLD-Framing/Rough-in | 8/30/2007 | 8/30/2007 | 8/30/2007 | P | PART |
Mike Jordan
|
|
|
Scheduled by a contractor via Hello! on 8/30/2007 at 10:38:05 AM. Contact: ###-####. Interior framed walls ok. One side only on 2 hr fire barrier wall. Needs UL data for roof drain thru penetrations for firestop.
|
BLD-Framing/Rough-in | 8/29/2007 | 8/30/2007 | 8/30/2007 | A | NR |
Mike Jordan
|
|
|
Scheduled by a contractor via Hello! on 8/29/2007 at 8:33:30 AM. Contact: ###-####. Elec. ri failed.
|
FIRE-Conference | 8/24/2007 | 8/24/2007 | 8/24/2007 | P | DONE |
Troy Cobbley
|
|
|
I let the electrician know that the manual pull station for the hood suppression system is to be mounted 10' to 20' from the hood in the path of egress.
|