BLD-Aging Inspection | 6/13/2008 | 6/13/2008 | 6/13/2008 | | PASS |
Jim Storey
|
|
|
|
DOC - Permit Finaled | 6/13/2008 | 6/13/2008 | 6/13/2008 | P | PASS |
Jim Storey
|
|
|
|
FIRE-Conference | 3/6/2008 | 3/13/2008 | 3/13/2008 | P | DONE |
Troy Cobbley
|
|
|
I defered questions on access through the conveyor system to mark senteno
|
BLD-Aging Inspection | 2/29/2008 | 3/6/2008 | 3/6/2008 | A | FAIL |
Troy Cobbley
|
|
|
I met with the manager and discussed the items remaining.
|
BLD-Aging Inspection | 2/28/2008 | 2/28/2008 | 2/29/2008 | | FAIL |
Jim Storey
|
|
|
need all permits and plans.
|
BLD-Final | 10/9/2007 | 10/10/2007 | 10/10/2007 | A | NR |
Jim Storey
|
|
|
Sunny If you need him there please call 30 min before going out Phone #: ###-#### pending fire c/n
|
FIRE-Final Inspection | 10/9/2007 | 10/9/2007 | 10/9/2007 | P | FAIL |
Troy Cobbley
|
|
|
Repair the two exit sign/emergency lights as marked on the plans. Provide the three new emergency lights as marked on the plans. Provide a racking permit for all of the racks that are currently being installed. The extended coverage upright heads located on both sides of the two hour demising wall are obstructed by the enveloped trusses. This work requires a separate sprinkler permit. Repair the roll down fire doors in the two hour demising wall or get permision to lock them shut from the Boise Fire Dept.
|
BLD-Wall cover | 9/4/2007 | 9/4/2007 | 9/4/2007 | P | PART |
Tom Arcoraci
|
|
|
Scheduled by a contractor via Hello! on 9/4/2007 at 10:19:57 AM. Contact: ###-####. wip ok pending elec plumb mech
|