BLD-Final | 10/20/2009 | 10/21/2009 | 10/20/2009 | A | PASS |
Jim Sly
|
|
|
bryan Phone #: ###-#### OK for Perm Occ.
|
FIRE-Final Inspection | 10/20/2009 | 10/20/2009 | 10/20/2009 | P | PASS |
Troy Cobbley
|
|
|
Life safety passed.
|
FIRE-Final Inspection | 10/5/2009 | 10/6/2009 | 10/6/2009 | P | FAIL |
Troy Cobbley
|
|
|
The occupant load signs have been mounted and the exit signs, emergency lighting and exit discharge lighting have been verified for functionality. One emergency light and one exit sign need repaired as discussed. See the 10/5/2009 entry for other items needing addressed prior to a final sign off. The relocation of the generator is ok per scott and the fire alarm panel can provide supervision of the primary power at the horizontal sliding doors per Jason Blaise.
|
FIRE-Final Inspection | 10/1/2009 | 10/5/2009 | 10/5/2009 | P | FAIL |
Troy Cobbley
|
|
|
The project related fire sprinkler and fire alarm permits need to be finaled, both of the horizontal sliding doors need to be adjusted so that they easily open manually, the atrium smoke evacuation system needs to be addressed, the exit discharge lighting needs to be removed from control by the photocells and electrical super vision of the horizontal sliding doors needs to be addressed. All of the exit signs, emergency lights and exit discharge lights need to be inspected for placement and tested for functionality after the generator switch over has been repaired. Also need to verify that the relocation of the emergency generator is ok with plan review.
|
BLD-Final | 9/16/2009 | 9/17/2009 | 9/17/2009 | A | PART |
Jim Sly
|
|
|
Phone #: ###-#### Internet Inspection Request from: Bryan Herb Checked out all sleeping rooms.....OK, but need all Req signatures for final.
|
BLD-Other | 9/10/2009 | 9/14/2009 | 9/14/2009 | P | PASS |
Jim Storey
|
|
|
Drop ceiling grid inspection Phone #: ###-#### Internet Inspection Request from: Bryan Herb
|
BLD-Other | 8/24/2009 | 8/25/2009 | 8/25/2009 | A | NR |
Jim Sly
|
|
|
Suspended ceiling Phone #: ###-#### Internet Inspection Request from: Bryan Herb
|
BLD-Energy code compliance | 5/26/2009 | 5/27/2009 | 5/27/2009 | A | PART |
Jim Sly
|
|
|
1st floor insulation Phone #: ###-#### Internet Inspection Request from: Bryan Herb........OK
|
BLD-Wall cover | 5/26/2009 | 5/26/2009 | 5/26/2009 | P | PASS |
Jim Sly
|
|
|
2nd floor sheetrock nailing Phone #: ###-#### Internet Inspection Request from: Bryan Herb
|
BLD-Wall cover | 5/20/2009 | 5/21/2009 | 5/21/2009 | A | PASS |
Jim Sly
|
|
|
sheetrock nailing 3rd floor hallways 1st layer Phone #: ###-#### Internet Inspection Request from: Bryan Herb
|
BLD-Energy code compliance | 5/19/2009 | 5/20/2009 | 5/20/2009 | A | PASS |
Jim Sly
|
|
|
2nd floor insulation Phone #: ###-#### Internet Inspection Request from: Bryan Herb
|
BLD-Energy code compliance | 5/15/2009 | 5/15/2009 | 5/15/2009 | P | PASS |
Jim Sly
|
|
|
3rd floor insulation Phone #: ###-#### Internet Inspection Request from: Bryan Herb
|
BLD-Framing/Rough-in | 5/13/2009 | 5/14/2009 | 5/14/2009 | A | PASS |
Jim Sly
|
|
|
1st and 2nd floor fire caulking Phone #: ###-#### Internet Inspection Request from: Bryan Herb
|
BLD-Wall cover | 5/11/2009 | 5/12/2009 | 5/12/2009 | P | PASS |
Jim Sly
|
|
|
reinspect draft stop on 3rd floor. Phone #: ###-#### Internet Inspection Request from: Bryan Herb
|
BLD-Framing/Rough-in | 5/8/2009 | 5/11/2009 | 5/11/2009 | A | PART |
Jim Sly
|
|
|
fire caulking 3rd floor Phone #: ###-#### Internet Inspection Request from: Bryan Herb
|
BLD-Wall cover | 4/20/2009 | 4/21/2009 | 4/21/2009 | A | PASS |
Jim Sly
|
|
|
1st and 2nd floor hallway fire caulking inspection Phone #: ###-#### Internet Inspection Request from: Bryan Herb
|
BLD-Framing/Rough-in | 2/26/2009 | 3/2/2009 | 3/2/2009 | P | PART |
Jim Sly
|
|
|
interior shear inspection Phone #: ###-#### Internet Inspection Request from: Bryan Herb Int Shear C wing OK.
|
BLD-Framing/Rough-in | 2/4/2009 | 2/5/2009 | 2/5/2009 | A | PART |
Jim Sly
|
|
|
Roof inspection Phone #: ###-#### Internet Inspection Request from: Bryan Herb Roof Nailing and straps appear OK BLDG C
|
BLD-Framing/Rough-in | 1/30/2009 | 2/2/2009 | 2/2/2009 | A | PART |
Jim Sly
|
|
|
exterior sheer wall C wing Phone #: ###-#### Internet Inspection Request from: Bryan Herb Exterior wall shear nailing OK Bldg C
|
BLD-Conference | 12/11/2008 | 12/12/2008 | 12/12/2008 | A | DONE |
Jim Sly
|
|
|
discussion of plumbing against 2hr fire wall Phone #: ###-#### Internet Inspection Request from: Bryan Herb
|
BLD-Concrete | 11/24/2008 | 11/25/2008 | 11/25/2008 | P | PART |
Jim Sly
|
|
|
MTI scheduled for 2:30 and concrete for 3:00 for interior footings in last wing. Phone #: ###-#### Internet Inspection Request from: Bryan Herb Interior Footings OK pending MTI insp, tests and approvals.
|
BLD-Energy code compliance | 10/13/2008 | 10/17/2008 | 10/17/2008 | A | PASS |
Jim Sly
|
|
|
foundation insulation Phone #: ###-#### Internet Inspection Request from: Bryan Herb
|
BLD-Foundation | 10/13/2008 | 10/14/2008 | 10/14/2008 | A | PART |
Jim Sly
|
|
|
Phone #: ###-#### Internet Inspection Request from: Bryan Herb Wall at west end OK pending MTI special insp, tests, and approvals.
w
|
BLD-Footing | 10/7/2008 | 10/8/2008 | 10/8/2008 | P | PART |
Jim Sly
|
|
|
Phone #: ###-#### Internet Inspection Request from: Bryan Herb West end. OK
w
|