Permit Information
Permit NumberBLD07-02423
StatusFinaled
Name THE WATER COOLER
Site Address 1401 W IDAHO ST
Project NameWATER COOLER BLDG
Customer Number 
ePlanReviewNo
Description
(THE WATER COOLER BUILDING - TENANT IMPROVEMENT) This building is NOT fire sprinklered. To remodel an existing 9,742 square foot building (8,550 square foot inside and 1,192 square foot covered storage) and convert it to office and storage use. Work is to include 2 restrooms accessible to the disabled, interior nonbearing walls, an interior stairway, interior doors, interior windows, millwork, and finishes. The 783 square foot basement is NOT approved for occupancy because it will NOT have a compliant egress system. An existing 1,565 square foot separate building on this site will be demolished. The parking lot work is not covered under this permit. Site work in the public way will be done in conjunction with this permit. A license agreement with ACHD governs the proposed construction in the public way. The work is required to comply with the approved drawings, with the plan review report, and with all applicable codes. The interior demolition work was covered under permit BLD07-01723. **CJW**
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
BLD-Final5/11/20085/12/20085/12/2008PPASS
DetailsTony Young
Scheduled by a contractor via Hello! on 5/11/2008 at 9:23:41 PM. Contact: ###-####.
signed on temp occ.,, but now see that all trades are signed off in comp. system,, final/perm. cof o is ok
FIRE-Final Inspection5/11/20085/12/20085/12/2008APASS
DetailsForrest France
Noted corrections have been completed, minor adjustments to duct sample tube orientation done while on site, fire life safety finaled.
Code Occupancy Approval5/9/20085/9/20085/9/2008PPASS
DetailsMichael Garner
Site inspection completed - work has been completed according to approved plans
BLD-Final5/9/20085/9/20085/9/2008PNR
DetailsDave Hannah
Scheduled by a contractor via Hello! on 5/9/2008 at 9:37:22 AM. Contact: ###-####. needs fire c/n items completed and finaled
FIRE-Final Inspection5/9/20085/9/20085/9/2008AFAIL
DetailsTroy Cobbley
Provide tags for the three fire extinguishers. Provide remote annunciators as discussed for the duct smoke detectors. The duct smoke detectors are mounted in the 90 degree elbows of the return air ducting. A manometer test will be required or the ducting modified to the 6 to 10 duct widths as per NFPA 72. All other items checked out ok.
FIRE-Final Inspection5/8/20085/8/20085/8/2008PNR
DetailsForrest France
Not ready at this time per phone call from contractor, to be rescheduled as discussed.
FIRE-Conference4/14/20084/14/20084/14/2008PDONE
DetailsForrest France
On site conference regarding door hardware, duct detectors and project fire code review notes.
BLD-Conference4/14/20084/14/20084/14/2008PPART
DetailsTony Young
andy Phone #: ###-####
conf w/ 430 on doors, landings, etc
BLD-Framing/Rough-in4/10/20084/10/20084/10/2008APASS
DetailsTony Young
Scheduled by a contractor via Hello! on 4/10/2008 at 7:08:34 AM. Contact: ###-####.
walls ok to cover
BLD-Framing/Rough-in4/3/20084/3/20084/3/2008APART
DetailsTony Young
Scheduled by a contractor via Hello! on 4/3/2008 at 6:52:06 AM. Contact: ###-####.
braces under mech rooftop units
BLD-Conference3/20/20083/20/20083/20/2008APART
DetailsTony Young
Scheduled by a contractor via Hello! on 3/20/2008 at 5:55:59 AM. Contact: ###-####.
draft stop ?s,, can do on existing ponywall framing,, other misc ?s,, ok