Permit Information
Permit NumberBLD07-02644
StatusFinaled
Name DAVE EVANS CONSTRUCTION
Site Address 7126 W VICTORY RD
Project NamePower Sports Planet
Customer Number 
ePlanReviewNo
Description
Power Sports Planet - To construct a new 14,500 square foot, one story motorcycle retail sales and repair facility and related site improvements. This building will contain a retail sales showroom, office area, parts storage area and repair garage. This building is a pre-engineered metal building with steel stud and wood framed wall construction. This building is at maximum allowable area. This building may not be added onto unless the building is fully fire sprinkled. All construction per the approved plans and attached comment list. JCM
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
BLD-Final12/29/200812/29/200812/29/2008PPASS
DetailsTom Arcoraci
jed Phone #: ###-####
FIRE-Final Inspection12/18/200812/18/200812/18/2008PPASS
DetailsTroy Cobbley
Life safety passed.
BLD-Final12/12/200812/15/200812/15/2008PPART
DetailsMike Jordan
JED Phone #: ###-####. Temp occ. granted. Still need letter from special insp. agency and is waiting for the remainder of door hardware for double doors. Also recieved letter with employees signatures stating that they were briefed and trained on manual flush bolts.
FIRE-Final Inspection12/12/200812/15/200812/15/2008APART
DetailsTroy Cobbley
A temporary occupancy was given with sam rogers permission until the fire hydrant is active. United Water installed it today and it will be active as soon as the thrust block has set up.
BLD-Other12/11/200812/11/200812/11/2008PFAIL
DetailsTom Arcoraci
Scheduled by a contractor via Hello! on 12/11/2008 at 7:40:27 AM. Contact: ###-####. Note: Please call 1/2 hr prior to inspection no manuel flush bolts allowed on double doors
FIRE-Conference12/8/200812/8/200812/8/2008PDONE
DetailsTroy Cobbley
I went over life safety requirements for this project. It appears per the fire review comments that a fire hydrant was to be installed out front and fire sprinklers/alarm systems were to be installed as well. These items have not been installed. Scott and Sam have been contacted.
BLD-Energy code compliance11/6/200811/7/200811/7/2008APASS
DetailsTom Arcoraci
jed Phone #: ###-####
BLD-Framing/Rough-in11/5/200811/6/200811/6/2008APART
DetailsTom Arcoraci
jed Note: please call 1/2 hr prior to inspection to meet with Phone #: ###-#### wip ok 3 hr wall
BLD-Wall cover10/31/200810/31/200810/31/2008PPART
DetailsTony Young
Scheduled by a contractor via Hello! on 10/31/2008 at 10:08:23 AM. Contact: ###-####.
office areas only ok to cover
BLD-Framing/Rough-in10/31/200810/31/200810/31/2008PPART
DetailsTony Young
Scheduled by a contractor via Hello! on 10/31/2008 at 10:07:52 AM. Contact: ###-####.
office areas only ok to cover,, still need to inspect 3 hr wall
BLD-Framing/Rough-in10/28/200810/28/200810/28/2008PFAIL
DetailsJim Storey
Scheduled by a contractor via Hello! on 10/28/2008 at 8:49:58 AM. c/n need floor trusses repair for top chord ele and plm cuts/ foam seal top plate penatrations fr fire blk./ nail fool trusses at hanger at header in hall/ provide listing for fire stopping of 3 hr wall/ provide r-38 verifcation of roof insulation. ok to insulate office partions.
BLD-Wall cover10/28/200810/28/200810/28/2008PPART
DetailsJim Storey
Scheduled by a contractor via Hello! on 10/28/2008 at 8:50:32 AM. gyp progression on b sir ok screw sch ok. need fire stop at floor cavity.
BLD-Footing9/2/20089/2/20089/2/2008PPASS
DetailsJim Sly
Scheduled by a contractor via Hello! on 9/2/2008 at 8:04:27 AM. Contact: ###-####.
Verified 21' rebar UFER installed
BLD-Footing8/27/20088/28/20088/28/2008APART
DetailsMike Jordan
jay Phone #: ###-####. wip. Needs to complete install of remaining verts. Reviewed geotech report for subgrade, ok for conc. Noted to Jay that periodoc special insp. is required for verification of mix design and rebar insp.
BLD-Footing8/27/20088/27/20088/27/2008PPART
DetailsMike Jordan
Phone #: ###-####. wip on installing reinforcement. Called contractor to have him contact a Geotech engineer to verify the min. 2000 psf soil bearing for footings. Will reschedule additional insp. for the am.