Permit Information
Permit NumberBLD07-02828
StatusFinaled
Name BOISE PROFESSIONAL MAINTANCE MGMT
Site Address 875 W MCGREGOR CT Unit: 150
Project NameFEDERAL WAY COMMERCE
Customer Number 
ePlanReviewNo
Description
(M2E POWER INC)(FEDERAL WAY COMMERCE - STE 150) To construct a lab room and a mill/lathe room in the warehouse portion of an existing 2-story office / storage tenant space of 9,926 sq.ft. ( 6,855 s.f 1st floor / 2,571 s.f. 2nd floor) per approved plans and engineering. Original tenant space constructed under BLD99-03562, EMI Co. Work to include construction of interior walls to create the 1,154 s.f prototype micro generator test lab and to create a separate 450 s.f. fabrication room making housing's for micro generators (see architects letter of explanation concerning lab and fab area use purpose attached to plans). Hot work shall be in compliance with 2003 IFC. Modification to sprinkler system requires separate application, approval & permit from fire dept. before work can be done. drs
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
BLD-Final1/31/20081/31/20081/31/2008PPASS
DetailsDave Hannah
don Phone #: ###-#### ok fo perm occ
FIRE-Final Inspection1/30/20081/31/20081/31/2008APASS
DetailsTroy Cobbley
Life safety passed
FIRE-Final Inspection1/25/20081/29/20081/29/2008AFAIL
DetailsForrest France
A fire alarm permit will be necessary to interconnect the new smoke detectors at the two FSD's to the FACP or provide an approved building plan modification for deletion of the dampers, need to remove the manual flush bolts at the lathe room inactive door leaf, also the fire sprinkler permit needs to be finaled prior to life safety.
FIRE-Sprinkler Rough-in1/28/20081/29/20081/29/2008AFAIL
DetailsForrest France
Mixed response heads are not allowed within the same fire area at the new lab and lathe rooms.
BLD-Other1/25/20081/28/20081/28/2008APART
DetailsJim Storey
don wilcox-drop down ceiling inspection please Phone #: ###-#### need clips or spreader bar / auto flush bolts on double doors.
BLD-Framing/Rough-in1/8/20081/8/20081/8/2008PPASS
DetailsJim Storey
don Phone #: ###-####