BLD-Final | 5/14/2009 | 5/14/2009 | 5/14/2009 | P | PASS |
Tony Young
|
|
|
Phone #: ###-#### Internet Inspection Request from: Jessica Noland final ok
|
DOC - Permit Finaled | 5/14/2009 | 5/14/2009 | 5/14/2009 | P | PASS |
Tony Young
|
|
|
|
BLD-Final | 5/13/2009 | 5/13/2009 | 5/13/2009 | P | NR |
Tom Arcoraci
|
|
|
Phone #: ###-#### Internet Inspection Request from: Jessica Noland pending zoning
|
BLD-Conference | 2/16/2009 | 2/17/2009 | 2/17/2009 | A | PART |
Tony Young
|
|
|
hand rail consult Phone #: ###-#### Internet Inspection Request from: Jessica Noland fire riser access hand rails can turn at bottom to stay out of public way
|
BLD-Final | 1/28/2009 | 1/29/2009 | 1/29/2009 | P | PART |
Tony Young
|
|
|
Phone #: ###-#### Internet Inspection Request from: Jessica Noland temp ok,, need to finish out side access,, ok for temp occ on 3rd floor
|
FIRE-Final Inspection | 1/28/2009 | 1/29/2009 | 1/29/2009 | A | PASS |
Troy Cobbley
|
|
|
life safety passed
|
FIRE-Final Inspection | 1/27/2009 | 1/28/2009 | 1/28/2009 | P | CANC |
Troy Cobbley
|
|
|
fire life safety Phone #: ###-#### Internet Inspection Request from: Jessica Noland Inspection cancelled from web by: Jessica Noland
|
BLD-Final | 1/27/2009 | 1/28/2009 | 1/28/2009 | P | CANC |
Tony Young
|
|
|
LATE PM PLEASE Phone #: ###-#### Internet Inspection Request from: Jessica Noland Inspection cancelled from web by: Jessica Noland
|
FIRE-Final Inspection | 1/26/2009 | 1/27/2009 | 1/27/2009 | P | CANC |
Troy Cobbley
|
|
|
The life safety can be finaled when the project related fire sprinkler permit is finaled.
|
FIRE-Final Inspection | 1/23/2009 | 1/26/2009 | 1/26/2009 | P | CANC |
Troy Cobbley
|
|
|
Need the project related fire alarm and fire sprinkler permits finaled first. I also ran out of time for the inspection today.
|
BLD-Conference | 1/22/2009 | 1/23/2009 | 1/23/2009 | P | PASS |
Tony Young
|
|
|
above ceiling inspection 1st and 2nd floor Phone #: ###-#### Internet Inspection Request from: Jessica Noland
|
BLD-Framing/Rough-in | 12/29/2008 | 12/30/2008 | 12/30/2008 | A | NR |
Tony Young
|
|
|
ceiling inspection to cover Phone #: ###-#### Internet Inspection Request from: Jessica Noland they were wanting a grid inspection on bld08=00594 for T.I.
|
BLD-Framing/Rough-in | 12/26/2008 | 12/29/2008 | 12/29/2008 | P | CANC |
Tony Young
|
|
|
ceiling inspection to cover. Phone #: ###-#### Internet Inspection Request from: Jessica Noland Inspection cancelled from web by: Jessica Noland
|
BLD-Framing/Rough-in | 12/24/2008 | 12/26/2008 | 12/26/2008 | A | PART |
Tony Young
|
|
|
above ceiling inspection for cover Phone #: ###-#### Internet Inspection Request from: Jessica Noland need mech r/in,, ok to drop perimeter tiles
|
BLD-Framing/Rough-in | 12/17/2008 | 12/18/2008 | 12/18/2008 | A | PART |
Mike Jordan
|
|
|
shaft wall inspection Phone #: ###-#### Internet Inspection Request from: Jessica Noland. shaft wall, 2nd. floor. ok
|
BLD-Wall cover | 12/10/2008 | 12/11/2008 | 12/11/2008 | A | PART |
Tony Young
|
|
|
shaft wall Phone #: ###-#### Internet Inspection Request from: Jessica Noland wip on 2nd and 3rd floor
|
BLD-Other | 12/10/2008 | 12/10/2008 | 12/10/2008 | P | PART |
Tony Young
|
|
|
shaft wall Phone #: ###-#### Internet Inspection Request from: Jessica Noland wip,, 2nd and 3rd floor
|
BLD-Conference | 12/9/2008 | 12/10/2008 | 12/10/2008 | A | PART |
Tony Young
|
|
|
shaft wall Phone #: ###-#### Internet Inspection Request from: Jessica Noland wip on 3rd floor shaft
|
BLD-Conference | 11/14/2008 | 11/17/2008 | 11/18/2008 | P | PART |
Tony Young
|
|
|
Hour Separation Wall Phone #: ###-#### ,, with 415 425 and 415 ,, will need fix from architect
|
DOC - Permit Finaled | 11/17/2008 | 11/17/2008 | 11/17/2008 | P | CANC |
Tony Young
|
|
|
(This activity was added in error so we have changed the case status back to Issued.)
|
BLD-Conference | 11/14/2008 | 11/17/2008 | 11/17/2008 | P | PART |
Dave Hannah
|
|
|
Hour Separation Wall Phone #: ###-#### Internet Inspection Request from: Jessica Noland
|
BLD-Conference | 11/14/2008 | 11/14/2008 | 11/14/2008 | P | FAIL |
Tony Young
|
|
|
Hour Separation Wall Phone #: ###-#### Internet Inspection Request from: Jessica Noland need to research and conf again,,
|
BLD-Framing/Rough-in | 11/6/2008 | 11/7/2008 | 11/7/2008 | P | PASS |
Tony Young
|
|
|
inspection to cover Phone #: ###-#### Internet Inspection Request from: Jessica Noland all walls ok to cover pending trades
|
FIRE-Conference | 10/31/2008 | 11/3/2008 | 11/3/2008 | A | DONE |
Troy Cobbley
|
|
|
Conference was for the placement of the electric alarm bell which I defered to the city approved sprinkler plans. I defered the knox box placement to Fire Station 9
|
BLD-Framing/Rough-in | 10/17/2008 | 10/17/2008 | 10/17/2008 | P | PASS |
Tony Young
|
|
|
SHEETROCK SCREW INSPECTION NORTH AND WEST SIDES Phone #: ###-#### Internet Inspection Request from: Jessica Noland
|
BLD-Framing/Rough-in | 10/15/2008 | 10/16/2008 | 10/16/2008 | P | FAIL |
Tony Young
|
|
|
drywall / screw inspection west side only Phone #: ###-#### Internet Inspection Request from: Jessica Noland need screwed off per schedule on plans
|
BLD-Framing/Rough-in | 10/15/2008 | 10/16/2008 | 10/15/2008 | A | CANC |
Tony Young
|
|
|
sheetrock/screw inspection west side only Phone #: ###-#### Internet Inspection Request from: Jessica Noland Inspection cancelled from web by: Jessica Noland
|
BLD-Framing/Rough-in | 10/10/2008 | 10/13/2008 | 10/13/2008 | A | PART |
Tony Young
|
|
|
soffit Phone #: ###-#### Internet Inspection Request from: Jessica Noland south soffits ok to cover
|
BLD-Framing/Rough-in | 9/25/2008 | 9/26/2008 | 9/26/2008 | P | PASS |
Tony Young
|
|
|
exterior framing inspection for cover north, south and east walls Phone #: ###-#### Internet Inspection Request from: Jessica Noland
|
BLD-Wall cover | 9/22/2008 | 9/23/2008 | 9/23/2008 | A | PART |
Mike Jordan
|
|
|
partial inspection of steel stud framing for west and north walls Phone #: ###-#### Internet Inspection Request from: Jessica Noland. ok to cover west wall exterior sise only. Additional screws added at headers.
|
BLD-Conference | 9/18/2008 | 9/22/2008 | 9/22/2008 | A | PART |
Tony Young
|
|
|
partial inspection of steel stud framing for west and north walls Phone #: ###-#### Internet Inspection Request from: Jessica Noland most ok on exterior,, need more screws on some areas
|
BLD-Other | 9/3/2008 | 9/4/2008 | 9/4/2008 | A | PART |
Tony Young
|
|
|
roof pan deck inspection; special inspector from MTI will be on site. Phone #: ###-#### Internet Inspection Request from: Jessica Noland ok pend special inspection report
|
BLD-Framing/Rough-in | 8/27/2008 | 9/2/2008 | 9/2/2008 | A | PART |
Dave Hannah
|
|
|
Roof Framing Phone #: ###-#### Internet Inspection Request from: Jessica Noland metal trusses on roof ok to cover
|
BLD-Concrete | 8/8/2008 | 8/11/2008 | 8/11/2008 | P | CANC |
Tony Young
|
|
|
Phone #: ###-#### Internet Inspection Request from: Jessica Noland
|
BLD-Other | 8/8/2008 | 8/8/2008 | 8/11/2008 | P | PART |
Tony Young
|
|
|
structural steel Phone #: ###-#### Internet Inspection Request from: Jessica Noland pending S. I.
|
BLD-Concrete | 8/8/2008 | 8/11/2008 | 8/8/2008 | A | CANC |
Tony Young
|
|
|
pouring 2nd & 3rd floors and stairs Monday a.m. Phone #: ###-#### Internet Inspection Request from: Jessica Noland Inspection cancelled from web by: Jessica Noland
|
BLD-Conference | 6/6/2008 | 6/9/2008 | 6/9/2008 | A | PART |
Tony Young
|
|
|
masonry rebar and grout pour 7am special inspector on site Phone #: ###-#### Internet Inspection Request from: Jessica Noland ok pend s. i. report
|
BLD-Conference | 6/3/2008 | 6/5/2008 | 6/5/2008 | A | PART |
Tony Young
|
|
|
masonry rebar and grout inspection special inspector on site at 7 am Phone #: ###-#### Internet Inspection Request from: Jessica Noland pend s. i. report
|
BLD-Conference | 6/3/2008 | 6/4/2008 | 6/4/2008 | A | PART |
Tony Young
|
|
|
masonry rebar and grout inspection special inspector on site at 10 am Phone #: ###-#### Internet Inspection Request from: Jessica Noland pend s i report
|
BLD-Concrete | 6/2/2008 | 6/3/2008 | 6/3/2008 | A | PART |
Tony Young
|
|
|
dan- special inspections will be onsite Phone #: ###-#### ok pend S. I. report
|
BLD-Conference | 5/15/2008 | 5/16/2008 | 5/16/2008 | P | PART |
Tony Young
|
|
|
rebar placement and grout pour @ Noon 12pm Phone #: ###-#### Internet Inspection Request from: Jessica Noland 1st coarse,, S. I. on site
|
BLD-Footing | 4/28/2008 | 4/29/2008 | 4/29/2008 | P | PART |
Tony Young
|
|
|
Phone #: ###-#### Internet Inspection Request from: Jessica Noland walls ok pending special inspection
|
BLD-Footing | 4/25/2008 | 4/29/2008 | 4/28/2008 | A | CANC |
Tony Young
|
|
|
Rebar Inspection Phone #: ###-#### Internet Inspection Request from: Jessica Noland Inspection cancelled from web by: Jessica Noland
|
BLD-Footing | 4/16/2008 | 4/18/2008 | 4/18/2008 | P | PART |
Tony Young
|
|
|
REBAR INSPECTION Phone #: ###-#### Internet Inspection Request from: Jessica Noland wip,, will have special inspection
|