BLD-Final | 8/19/2008 | 8/20/2008 | 8/20/2008 | A | PASS |
Jim Sly
|
|
|
toby Phone #: ###-#### OK for Perm OCC.
|
FIRE-Final Inspection | 8/15/2008 | 8/18/2008 | 8/19/2008 | A | PASS |
Troy Cobbley
|
|
|
life safety passed
|
FIRE-Final Inspection | 8/18/2008 | 8/19/2008 | 8/19/2008 | A | PASS |
Troy Cobbley
|
|
|
Life safety passed
|
BLD-Final | 8/15/2008 | 8/18/2008 | 8/18/2008 | A | DONE |
Jim Sly
|
|
|
Barb-Jim & Troy-This is on my list of coming due to expire occupancy-could you please check on it and let me know-also let GC know 7 days till expire.Thanks Phone #: ###-#### I called Toby Norton and explained......He said he would call in final inspections......
|
BLD-Final | 5/27/2008 | 5/27/2008 | 5/27/2008 | P | PART |
Jim Sly
|
|
|
OK for Temp Occ.
|
FIRE-Final Inspection | 5/23/2008 | 5/23/2008 | 5/23/2008 | P | PART |
Forrest France
|
|
|
Site visit performed by S. Rogers. Acceptable for TOC. Maglocks on doors were approved by Mark Senteno, Asst. FM, to not have motion detection release, however, the required manual push button release does not maintain the doors unlocked for the required minimum 30 seconds (Ref IFC 1008.1.3.4 item 3). It relocks immediately upon release of the push button. For Temp Occy approval, the mag lock circuit was electrically bypassed (dedicated circuit breaker tripped, within the locked electrical panel). The P&R contact, Toby, indicated Parks will manually lock and unlock the doors each day, as they currently do at many other facilities, until they get the required timer installed and field approved by PDS/Fire. All other Fire/Life Safety items were satisfactory. SLR.
|
BLD-Final | 5/21/2008 | 5/22/2008 | 5/22/2008 | P | NR |
Jim Sly
|
|
|
toby Note: please call 1/2 hr prior to inspection Phone #: ###-#### OK for perm occ.......when Fire signs for Perm Occ.
|
FIRE-Final Inspection | 5/21/2008 | 5/22/2008 | 5/22/2008 | A | CANC |
Troy Cobbley
|
|
|
Could not get power to building to test mag locks.
|
FIRE-Final Inspection | 5/21/2008 | 5/21/2008 | 5/21/2008 | P | FAIL |
Troy Cobbley
|
|
|
I left two messages and received no responce. There was no access to the restrooms.
|
BLD-Final | 5/21/2008 | 5/21/2008 | 5/21/2008 | P | CANC |
Jim Sly
|
|
|
Cheyne; Phone #: ###-#### x309 Internet Inspection Request from: Cathy Weisshaupt
|