Permit Information
Permit NumberBLD08-00201
StatusFinaled
Name INDUSTRIAL INSULATION SYSTEMS INC.
Site Address 525 N STEELHEAD WAY
Project Name 
Customer Number 
ePlanReviewNo
Description
**(Industrial Insulation Systems Inc.)** Application for inspection to determine requirements for issuance of a Certificate of Occupancy for an existing 14,012 sq ft tenant space to be used as a light manufacturing / warehouse & office space. NO NEW WORK IS AUTHORIZED UNDER THIS PERMIT. This space was formerly occupied by "Johnstone supply" NO RACKING OVER EIGHT FEET HIGH IS ALLOWED UNDER THIS PERMIT. A SEPARATE PERMIT WILL BE REQUIRED TO INSTALL RACKING OVER EIGHT FEET HIGH. there are no changes to use or occupancy under this permit. RmH
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
FIRE-Final Inspection3/5/20083/5/20083/5/2008PPASS
DetailsTroy Cobbley
Life safety passed. The original parts have been re-installed in the facp. Mountain Alarm was hired to verify that everything was working. I requested a representative to be present to test the system and found that zones #9 and #10 needed to be swapped. The second phone line is functional. The handle on the PIV is not permanantly mounted. I told the onsite tenant representative to contact a fire sprinkler company to get the replacement bolt. The PIV is still functional.
BLD-Final3/5/20083/6/20083/5/2008APASS
DetailsMike Jordan
dan Phone #: 724-632. ok for perm occ.
BLD-Final2/29/20083/3/20083/3/2008PNR
DetailsMike Jordan
Dan; Phone #: ###-#### Internet Inspection Request from: Cathy Weisshaupt. Life/safety failed.
FIRE-Final Inspection2/29/20082/29/20083/3/2008PFAIL
DetailsTroy Cobbley
All life safey items have been corrected except for the fire alarm panel. The tenant hired "The Fire Alarm Guy" to get the system running again. I contacted him to verify different items and found that the circuit board of the panel had been replaced with another. Also there is only one phone line active. Per the monitoring company the tamper zone is rolling the fire trucks. I informed Mark that permits are required for this type of work and that he should contact sam rogers for further information. I contacted sam as well.
FIRE-Final Inspection2/21/20082/22/20082/22/2008AFAIL
DetailsTroy Cobbley
Provide emergency lighting in the warehouse, remove the thumbturn lock from the main exit, provide indicator at the main exit lock, install all ceiling tile, provide covers on the electrical outlets, provide verification that the fire alarm system is functional, provide approved hardware on the warehouse exit doors and the north facing showroom door.
BLD-Final2/21/20082/22/20082/22/2008PFAIL
DetailsMike Jordan
Dan ###-#### // please call 30 min prior to meet for access, the building is locked. life/safety failed.