BLD-Aging Inspection | 2/24/2009 | 2/24/2009 | 2/24/2009 | | PASS |
Jim Storey
|
|
|
final ok
|
DOC - Permit Finaled | 2/24/2009 | 2/24/2009 | 2/24/2009 | P | PASS |
Jim Storey
|
|
|
|
BLD-Final | 12/23/2008 | 12/23/2008 | 12/23/2008 | P | PART |
Jim Storey
|
|
|
Scheduled by a contractor via Hello! on 12/23/2008 at 8:08:15 AM. Contact: ###-####. final occ ok pending plm perm occ. sign off.
|
FIRE-Final Inspection | 12/16/2008 | 12/17/2008 | 12/17/2008 | A | PASS |
Forrest France
|
|
|
Correction items repaired and verified for functionality, fire life safety finaled.
|
FIRE-Final Inspection | 12/15/2008 | 12/16/2008 | 12/16/2008 | A | FAIL |
Forrest France
|
|
|
Need to test the new door mag lock for drop out on fire alarm condition, four exit signs are not functional on backup power source, inspection concluded at this time-to be rescheduled.
|
FIRE-Final Inspection | 11/28/2008 | 11/28/2008 | 11/28/2008 | P | NH |
Forrest France
|
|
|
|
BLD-Other | 10/30/2008 | 10/30/2008 | 10/30/2008 | P | PASS |
Jim Storey
|
|
|
shaft complet in attic from gas room to exterior.
|
BLD-Conference | 10/28/2008 | 10/29/2008 | 10/29/2008 | P | PART |
Jim Storey
|
|
|
Scheduled by a contractor via Hello! on 10/28/2008 at 3:37:58 PM. Contact: ###-####. shaft complet up to small sections from ceilling to horisontal section and face peice at elbow north end above entry door. ok to finsh check at ceilling insp.
|
FIRE-Final Inspection | 10/27/2008 | 10/27/2008 | 10/27/2008 | A | NR |
Forrest France
|
|
|
Need project related fire sprinkler permit final prior to building life safety approval.
|
BLD-Conference | 10/23/2008 | 10/24/2008 | 10/24/2008 | P | PART |
Jim Storey
|
|
|
dave Phone #: ###-#### shaft sides ok.
|
BLD-Framing/Rough-in | 10/15/2008 | 10/15/2008 | 10/17/2008 | P | PART |
Jim Storey
|
|
|
dave Phone #: ###-#### gas rm not aproved and will need resolved by arch. to meet bld and fire code requirments not addressed on the plan. insulation of the rest of the ti space ok.
|
BLD-Aging Inspection | 9/8/2008 | 9/8/2008 | 9/8/2008 | | NR |
Jim Storey
|
|
|
|