Permit Information
Permit NumberBLD08-01188
StatusFinaled
Name SPARKS COMMERCIAL CONTRACTING
Site Address 529 W ROSSI ST
Project NameICONIC VILLAGE
Customer Number 
ePlanReviewNo
Description
(ICONIC VILLAGE - LEASING OFFICE/COMMUNITY CENTER/BUSINESS CTR) To remodel an existing 990 sq.ft. Leasing office to a community center with a leaseing/business center.Work to include: two new accessible compliant restrooms, lounge area for tenants, enclose adjacent breezeway to add 210 sq.ft., enlarge existing openings, remove existing vinyl windows, and install aluminum storefront system. New flooring to be a combination of stained concrete + carpet/tile, new paint, and new millwork per approved plans, engineering, plan review report, CUP 08-00073 & DRH08-00152. This building does not have fire sprinklers. *SRZ*
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
BLD-Aging Inspection5/18/20095/18/20095/18/2009 DONE
DetailsJim Storey
DOC - Permit Finaled5/18/20095/18/20095/18/2009PPASS
DetailsJim Storey
BLD-Aging Inspection2/27/20092/27/20093/2/2009 DONE
DetailsJim Storey
BLD-Final9/22/20089/23/20089/23/2008APASS
DetailsJim Storey
andy Phone #: ###-#### l/c
BLD-Grading Inspection9/18/20089/18/20089/18/2008PPASS
DetailsDave Hannah
BLD-Final9/18/20089/18/20089/18/2008PFAIL
DetailsDave Hannah
needs to lower sinks landing outside of backdoor
FIRE-Final Inspection9/17/20089/17/20089/18/2008PPASS
DetailsForrest France
C/N is completed with the exception of the landing at the south exit-to be finished prior to structural final, hardware at the interveining door changed to passage, life safety passed.
BLD-Final9/17/20089/18/20089/18/2008ANR
DetailsDave Hannah
andy Phone #: ###-#### needs other trades to final first
FIRE-Final Inspection9/16/20089/16/20089/16/2008PFAIL
DetailsForrest France
Need to post building address numbers, missing max. occupant load sign per review notes, threshold at the south exit discharge is not yet finished, door hardware at the intervening space does not comply with IFC 2006 1014.2 (2.) (3.).
BLD-Energy code compliance8/8/20088/11/20088/11/2008APASS
DetailsJim Storey
vic Phone #: ###-####
BLD-Framing/Rough-in8/8/20088/11/20088/11/2008APASS
DetailsJim Storey
vic Phone #: ###-####
BLD-Conference8/1/20088/1/20088/1/2008PPART
DetailsJim Storey
Scheduled by a contractor via Hello! on 8/1/2008 at 10:01:50 AM. Contact: ###-####. first layer of ceilling assembly ok for cover.
BLD-Conference7/18/20087/21/20087/21/2008APASS
DetailsJim Storey
Scheduled by a contractor via Hello! on 7/18/2008 at 2:09:10 PM. Contact: ###-####. reviewed 2 hr ceilling aplacation.