BLD-Final | 11/20/2008 | 11/21/2008 | 11/21/2008 | A | PASS |
Tom Arcoraci
|
|
|
larry Note: open at 9:00 am Phone #: ###-####
|
FIRE-Final Inspection | 11/20/2008 | 11/20/2008 | 11/20/2008 | P | PASS |
Forrest France
|
|
|
All corrections were made per Troys last inspection. Racks were removed and wall in bathroom corridoor was removed to for sprinkler coverage issues. See notes from last inspection. KR
|
BLD-Final | 8/1/2008 | 8/4/2008 | 8/4/2008 | P | FAIL |
Jim Storey
|
|
|
tony- Phone #: ###-#### same as fire c/n and address numbers to the list.
|
FIRE-Final Inspection | 8/1/2008 | 8/4/2008 | 8/4/2008 | A | FAIL |
Troy Cobbley
|
|
|
Provide sprinkler protection in the restroom corridor, mount the "Door to Remain Unlocked...." sticker at the main exit where is is viewable, provide single action hardware as discussed at the south secondary exit door and provide a racking permit for the storage racks in the warehouse area. These racks exceed 8'-0" in height. They are roughly 9'-3" in height with carpet acouple of feet above that. Also the shelving is solid and the carpet and foam rolls are encapsulated. Also cars are being stored in the same area.
|