Permit Information
Permit NumberBLD08-01682
StatusFinaled
Name ELDREDGE CORP
Site Address 1689 S ENTERTAINMENT AVE
Project NameBeds Today
Customer Number 
ePlanReviewNo
Description
Beds Today - To construct a new 5,200 square foot, one story wood framed retail building and related site improvements. All construction per the approved plans and attached comment list. JCM 4-5-10 FINAL CERT OF VALUE PER GC $0409-990.00
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
BLD-Conference2/3/20102/4/20102/5/2010PPASS
DetailsJim Sly
Todd ###-####
Complaints from Neighbors adjacent to rearof bldg. Lighting at rear of bldg is shining on residential housing and keeping occupants awake. Worked with Contr and had him install shroud around lights.
BLD-Final2/4/20102/4/20102/4/2010PPASS
DetailsMike Jordan
Todd Phone #: ###-####. ok for perm occ.
BLD-Conference2/2/20102/3/20102/3/2010PCANC
DetailsJim Sly
Todd phone ###-#### Re-sched.....
BLD-Conference2/3/20102/3/20102/3/2010PCANC
DetailsJim Sly
Todd ###-####
BLD-Conference1/28/20102/2/20102/2/2010ACANC
DetailsJim Sly
Call Todd at ###-#### Check to see if he put a shroud over light at back of bldg.
Not done yet...Re-sched.......
BLD-Final1/27/20101/28/20101/28/2010APART
DetailsJim Sly
Todd Phone #: ###-####
OK for Temp Occ. Talked to Todd about Zoning on Temp...(Bicycle rack).
BLD-Final1/26/20101/26/20101/26/2010PNR
DetailsMike Jordan
Todd Phone #: ###-####. Everything ok, Mech failed. Needs to recall insp. once mech has passed.
FIRE-Final Inspection1/25/20101/25/20101/25/2010PPASS
DetailsTroy Cobbley
Life safety passed.
FIRE-Final Inspection1/20/20101/21/20101/21/2010AFAIL
DetailsTroy Cobbley
Provide single action hardware on door 101 and provide verification of the hvac systems velocity for possible duct smoke detector requirements.
BLD-Framing/Rough-in11/12/200911/13/200911/13/2009APASS
DetailsMike Jordan
TODD (DRAFT STOP IN FIRE WALL) Phone #: ###-####. Draft stop and nailing on interior side of 1hr. firewall ok.
BLD-Energy code compliance11/10/200911/10/200911/10/2009PPASS
DetailsMike Jordan
Insul. ok.
BLD-Framing/Rough-in11/10/200911/10/200911/10/2009PPASS
DetailsMike Jordan
BLD-Energy code compliance11/10/200911/10/200911/10/2009ACANC
DetailsMike Jordan
###-#### Todd
BLD-Framing/Rough-in11/5/200911/6/200911/6/2009APART
DetailsMike Jordan
Todd Phone #: ###-####. Interior framed walls and hardlid only. Needs to provide truss engineering. Also needs to install draftstop.
BLD-Framing/Rough-in11/4/200911/4/200911/4/2009PPART
DetailsMike Jordan
Todd-Sheating inspection please Phone #: ###-####. exterior 5/8 typex rock for north wall. ok.
BLD-Framing/Rough-in11/3/200911/3/200911/3/2009PPART
DetailsMike Jordan
todd Phone #: ###-####. 5/8 type x rock for 1hr.wall at parapet, northwall.
BLD-Conference11/2/200911/2/200911/2/2009PPART
DetailsJim Storey
todd Phone #: ###-#### exterior ok to cover/ need gyp to roof deck and 30 inches above paripett/ interior gyp needed from ceilling to roof deck/ strapping ok for sheer.
BLD-Framing/Rough-in10/28/200910/28/200910/28/2009PFAIL
DetailsMike Jordan
Todd Phone #: ###-####. Need new UL from architect on north 1hr extering bearing wall. Engineering showing that shear values will be equivelant with 5/8 typex rock instead of 7/16 ply. Also complete straping.
BLD-Foundation9/30/20099/30/20099/30/2009PPART
DetailsMike Jordan
jack Phone #: ###-####. wip on installing holddowns. All rebar in place.
BLD-Footing9/25/20099/28/20099/28/2009APART
DetailsMike Jordan
Todd Phone #: ###-####. perimeter footings. wip on east footing line. Allother is complete.