Permit Information
Permit NumberBLD08-01847
StatusFinaled
Name SIMPLOT CO
Site Address 5383 W IRVING ST
Project Name 
Customer Number 
ePlanReviewNo
Description
(SIMPLOT INFORMATION AND TECHNOLOGY BUILDING) Permit to construct a 485 square foot addition onto an existing 7,280 square foot building. New addition will be used as a mechanical room. The addition is less than 10 percent of the floor area and therefore is considered accessory occupancy per section 508.3.1 of the 2006 IBC. Work to include: construction of new exterior walls, construction of new roof system over the proposed addition, new site work (sidewalks, landings, and landscaping), new doors, installation of new mechanical units, and installation of interior finishes in compliance with chapter 8 of the IBC. This building is fully fire sprinklered any alterations or modifications to the sprinkler system WILL REQUIRE A SEPARATE PERMIT and shall be installed per NFPA #13 as regulated by the fire department. Planning approval done under DRH08-00267. **TLW**
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
FIRE-Final Inspection5/18/20105/19/20105/19/2010PPASS
DetailsTroy Cobbley
Life safety passed.
FIRE-Conference5/18/20105/18/20105/18/2010PDONE
DetailsScott Arellano
*ON SITE VISIT* The exterior building measurements that I took indicate a building length of 150.5 feet and a width of 51 feet; for a total fire flow calculation area of 7,676 sq.ft.. The fire flow documentation provided indicates an available fire flow of 2,250 gpm, which is adequate for type VB construction up to 7,700 sq.ft.. No fire flow reduction is necessary for the addition to this building; and therefore the existing fire protection systems are treated as non-required fire protection.
However, for City records this building shall not be considered a fully fire sprinklered building, and therefore will not qualify for any provisions of the IBC or IFC which would otherwise be predicated on a fully fire sprinklered building. Additionally, the existing alternative extinguishing system, located in the data center room would not qualify for any code reductions as if it were a fully fire sprinklered building.
BLD-Aging Inspection5/10/20105/10/20105/10/2010 PART
DetailsTom Arcoraci
BLD-Aging Inspection3/8/20103/8/20103/8/2010 PART
DetailsTom Arcoraci
waiting on sprinkler issue
BLD-Final1/5/20101/5/20101/5/2010APASS
DetailsJim Storey
final ok
BLD-Final12/21/200912/21/200912/21/2009APART
DetailsJim Storey
Please call 1 hour prior to inspection so I can arrange access to the building. Thank you, Mark Phone #: ###-#### Internet Inspection Request from: Mark Bowen need final letter for si/ no card on site final will be ok upon si report review.
FIRE-Final Inspection12/17/200912/18/200912/18/2009APASS
DetailsTroy Cobbley
Life safety passed.
FIRE-Final Inspection12/7/200912/7/200912/7/2009PFAIL
DetailsTroy Cobbley
Provide signage on both doors as discussed and repair the existing exit signs. Per Mark and the electricain the electrical service is under the 1,200 amp thres hold for the panic hardware requirement.
BLD-Aging Inspection10/5/200910/5/200910/5/2009 PASS
DetailsTom Arcoraci
BLD-Aging Inspection6/19/20096/19/20096/19/2009 PASS
DetailsTom Arcoraci
wip ok
BLD-Aging Inspection4/14/20094/14/20094/14/2009 PASS
DetailsTom Arcoraci
BLD-Framing/Rough-in2/11/20092/11/20092/11/2009APASS
DetailsTom Arcoraci
Please call 30 min. prior to arrival.
Thank you Phone #: ###-#### Internet Inspection Request from: Mark Bowen
BLD-Aging Inspection1/29/20091/29/20091/29/2009 PASS
DetailsTom Arcoraci
BLD-Foundation11/25/200811/26/200811/26/2008APASS
DetailsTom Arcoraci
Concrete scheduled for 10:00AM Phone #: ###-#### Internet Inspection Request from: Mark Bowen
BLD-Footing11/24/200811/25/200811/25/2008APASS
DetailsTom Arcoraci
Phone #: ###-#### Internet Inspection Request from: Mark Bowen