Information based on query as of Wednesday, July 17, 2024.
Permit Information
Permit NumberBLD09-00173
StatusFinaled
Name ELK RUN CONSTRUCTION LLC
Site Address 12349 W MCMILLAN
Project NameScott Wright Dental Office
Customer Number 
ePlanReviewNo
Description
Scott Wright Phase II Office - Scott Wright Dental Office -Tenant Improvement- To finish a 4,920 square foot dental office tenant improvement on the north side of a new shell building. The shell is being constructed at the same time as the finish on of this tenant space. The shell permit number is BLD09-00174. --- 4/22/09 Plans modified to between grid lines #1 & #1.5 and #E & #D to eliminate private restroom and rearrange floor plan in laundry and storage areas. All construction per the approved plans and attached comment list. JCM
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
BLD-Final8/6/20098/6/20098/6/2009PPASS
DetailsJim Sly
Jim Phone #: ###-####
OK for Perm Occ.
BLD-Final7/31/20098/3/20098/3/2009PNR
DetailsJim Sly
Jim Phone #: ###-####
Need Plumb Final for Perm Occ
BLD-Final7/30/20097/31/20097/31/2009APART
DetailsMike Jordan
Jim Phone #: ###-####. ok for temp occ. Needs to install mirrors in ada restroom and get plumding perm. occ.
FIRE-Final Inspection7/30/20097/31/20097/31/2009APASS
DetailsTroy Cobbley
Life safety passed
BLD-Final7/23/20097/30/20097/30/2009PNR
DetailsTony Young
Jim Phone #: ###-####
need trades 1st,, no inspection made
FIRE-Final Inspection7/28/20097/30/20097/30/2009AFAIL
DetailsTroy Cobbley
Not all of the door hardware has been installed and the vents for the medical gas room have been installed in the interior door instead of the exterior wall as required by code.
FIRE-Conference7/29/20097/29/20097/30/2009PDONE
DetailsTroy Cobbley
I discussed life safety items with the general contractor.
FIRE-Final Inspection7/23/20097/28/20097/28/2009AFAIL
DetailsForrest France
Missing door hardware at various locations, shell building permit needs called for final, project related fire sprinkler permit must be requested for inspection and finaled prior to tenant life safety approval, noted missing signage and valve locks at the DCVA serving the fire sprinkler piping, discussed fire code review notes and general requirements.
BLD-Framing/Rough-in7/15/20097/16/20097/16/2009APASS
DetailsJim Sly
Ceiling grid inspection please-Tim or Jim at ###-#### Phone #: ###-####
BLD-Conference7/9/20097/9/20097/9/2009PDONE
DetailsJim Sly
Pat Phone #: ###-####
BLD-Energy code compliance6/11/20096/11/20096/11/2009PPASS
DetailsJim Sly
tim Phone #: ###-####
Frame and energy pass
BLD-Framing/Rough-in5/15/20095/18/20095/18/2009APASS
DetailsJim Sly
Rick Phone #: ###-####
BLD-Framing/Rough-in4/28/20094/29/20094/29/2009APART
DetailsDave Hannah
rick - visual of ceiling Phone #: ###-#### trusses ok ok to hang lid
BLD-Other4/10/20094/10/20094/10/2009PPART
DetailsJim Sly
Rick- sheer wall Phone #: ###-####
S. & W. walls OK for hold down placement and attachment.