FIRE-Final Inspection | 7/20/2010 | 7/21/2010 | 7/21/2010 | A | PASS |
Troy Cobbley
|
|
|
life safety passed
|
BLD-Conference | 6/11/2010 | 6/11/2010 | 6/11/2010 | P | PASS |
Tom Arcoraci
|
|
|
|
BLD-Final | 6/11/2010 | 6/11/2010 | 6/11/2010 | P | PASS |
Tom Arcoraci
|
|
|
temp glass ok
|
BLD-Final | 6/1/2010 | 6/2/2010 | 6/2/2010 | A | PART |
Tom Arcoraci
|
|
|
harvey Phone #: ###-#### will use approved film for temp glass issues
|
BLD-Final | 5/28/2010 | 6/1/2010 | 6/1/2010 | P | NR |
Dave Hannah
|
|
|
Phone #: ###-####
|
FIRE-Final Inspection | 5/28/2010 | 6/1/2010 | 6/1/2010 | A | FAIL |
Troy Cobbley
|
|
|
Provide test report for the kitchen hood and the fire sprinkler permit needs to be finaled. Alarm permit finaled today. Occupant load signs for the assembly areas are temporary until the permanent ones are installed.
|
FIRE-Final Inspection | 5/27/2010 | 5/28/2010 | 5/28/2010 | A | FAIL |
Troy Cobbley
|
|
|
The only item for life safety that was inspected today were the exit signs and emergency lighting. One exit sign needs to be added as shown on the city approved plans. Herb is calling in for a re-inspection for Tuesday.
|
FIRE-Conference | 5/26/2010 | 5/27/2010 | 5/27/2010 | A | DONE |
Troy Cobbley
|
|
|
Trip test on smoke detectors--Matt Phone #: ###-####
|
FIRE-Final Inspection | 5/26/2010 | 5/26/2010 | 5/27/2010 | P | CANC |
Troy Cobbley
|
|
|
Wrong inspection type called in. Herb needed fire alarm inspection.
|
BLD-Conference | 5/24/2010 | 5/25/2010 | 5/25/2010 | P | PART |
Tom Arcoraci
|
|
|
|
BLD-Conference | 5/21/2010 | 5/24/2010 | 5/24/2010 | A | PASS |
Tom Arcoraci
|
|
|
|
BLD-Conference | 5/20/2010 | 5/21/2010 | 5/21/2010 | A | PASS |
Tom Arcoraci
|
|
|
|
BLD-Conference | 5/19/2010 | 5/20/2010 | 5/20/2010 | A | PART |
Mike Jordan
|
|
|
room in smoke compartment 4. needsz safety glazing.
|
BLD-Conference | 5/19/2010 | 5/19/2010 | 5/19/2010 | P | PART |
Tom Arcoraci
|
|
|
tempered glass required
|
BLD-Wall cover | 3/25/2010 | 3/26/2010 | 3/26/2010 | A | PASS |
Tom Arcoraci
|
|
|
|
BLD-Wall cover | 3/17/2010 | 3/24/2010 | 3/24/2010 | A | PASS |
Tom Arcoraci
|
|
|
|
BLD-Wall cover | 3/12/2010 | 3/17/2010 | 3/17/2010 | A | PASS |
Tom Arcoraci
|
|
|
|
FIRE-Conference | 3/12/2010 | 3/12/2010 | 3/12/2010 | P | DONE |
Troy Cobbley
|
|
|
Tom, building inspector, and I spoke to Herd about fire blocking and fire sprinkler requirements at the two fireplace locations and the columns. Also the the entire south third of the building has been covered with out the sprinkler piping having been inspected. I notified Herd of IFC requirements but stated that for this one specific happening I would not require the ceiling to be removed but the insulation would be required to be removed from over the piping for an inspection. The insulation will then need to be reinstalled for a secondary inspection. Any areas that I deam accessible will have the ceilings removed for sprinkler piping inspection. I notified Scott of the situation.
|
BLD-Framing/Rough-in | 3/12/2010 | 3/12/2010 | 3/12/2010 | P | PASS |
Tom Arcoraci
|
|
|
|
BLD-Framing/Rough-in | 3/10/2010 | 3/11/2010 | 3/11/2010 | P | FAIL |
Tom Arcoraci
|
|
|
herb Phone #: ###-####
|
BLD-Wall cover | 3/10/2010 | 3/11/2010 | 3/11/2010 | P | PASS |
Tom Arcoraci
|
|
|
|
BLD-Other | 2/25/2010 | 3/4/2010 | 3/4/2010 | A | PART |
Tom Arcoraci
|
|
|
work ij progress ok
|
BLD-Wall cover | 2/22/2010 | 2/25/2010 | 2/25/2010 | A | PASS |
Tom Arcoraci
|
|
|
|
BLD-Conference | 2/17/2010 | 2/24/2010 | 2/24/2010 | A | PASS |
Tom Arcoraci
|
|
|
|
BLD-Wall cover | 2/19/2010 | 2/22/2010 | 2/22/2010 | A | PART |
Tom Arcoraci
|
|
|
Herb Phone #: ###-#### wip
|
BLD-Conference | 2/10/2010 | 2/17/2010 | 2/17/2010 | A | PASS |
Tom Arcoraci
|
|
|
wip ok
|
BLD-Wall cover | 2/11/2010 | 2/12/2010 | 2/12/2010 | A | PASS |
Tom Arcoraci
|
|
|
Herb Phone #: ###-####
|
BLD-Other | 2/4/2010 | 2/10/2010 | 2/10/2010 | A | PASS |
Tom Arcoraci
|
|
|
|
BLD-Conference | 1/29/2010 | 2/3/2010 | 2/3/2010 | A | PASS |
Tom Arcoraci
|
|
|
|
BLD-Wall cover | 1/27/2010 | 1/29/2010 | 1/29/2010 | A | PART |
Tom Arcoraci
|
|
|
Herb Phone #: ###-#### wip ok
|
BLD-Framing/Rough-in | 1/22/2010 | 1/25/2010 | 1/25/2010 | A | PASS |
Tom Arcoraci
|
|
|
Curt-Cover inspection please Phone #: ###-####
|
FIRE-Conference | 1/20/2010 | 1/20/2010 | 1/20/2010 | P | DONE |
Troy Cobbley
|
|
|
The stop work order that had been previously posted for the fire alarm installation is being lifted due to the fire alarm plans being issued.
|
BLD-Wall cover | 1/20/2010 | 1/20/2010 | 1/20/2010 | A | FAIL |
Tom Arcoraci
|
|
|
fire stopping incomplete
|
BLD-Conference | 1/11/2010 | 1/19/2010 | 1/19/2010 | A | PASS |
Tom Arcoraci
|
|
|
wip ok
|
BLD-Framing/Rough-in | 1/8/2010 | 1/11/2010 | 1/11/2010 | P | PART |
Tom Arcoraci
|
|
|
Herb-Nailing inspection please Phone #: ###-#### wip ok
|
BLD-Other | 1/7/2010 | 1/7/2010 | 1/7/2010 | A | PASS |
Tom Arcoraci
|
|
|
discussed fire walls
|
BLD-Conference | 12/31/2009 | 1/6/2010 | 1/6/2010 | A | PASS |
Tom Arcoraci
|
|
|
|
BLD-Conference | 12/30/2009 | 12/31/2009 | 12/31/2009 | A | PASS |
Tom Arcoraci
|
|
|
|
BLD-Other | 12/23/2009 | 12/30/2009 | 12/30/2009 | A | PASS |
Tom Arcoraci
|
|
|
|
BLD-Wall cover | 12/17/2009 | 12/23/2009 | 12/23/2009 | A | PART |
Tom Arcoraci
|
|
|
wip ok
|
BLD-Conference | 12/17/2009 | 12/18/2009 | 12/18/2009 | P | PASS |
Tom Arcoraci
|
|
|
can lights ok
|
BLD-Other | 12/10/2009 | 12/17/2009 | 12/17/2009 | A | PASS |
Tom Arcoraci
|
|
|
wip ok
|
BLD-Wall cover | 12/4/2009 | 12/9/2009 | 12/10/2009 | P | PASS |
Tom Arcoraci
|
|
|
wip
|
BLD-Conference | 12/3/2009 | 12/4/2009 | 12/4/2009 | A | PASS |
Tom Arcoraci
|
|
|
wip ok discussed acces reach
|
BLD-Wall cover | 12/2/2009 | 12/3/2009 | 12/3/2009 | A | PASS |
Tom Arcoraci
|
|
|
wip
|
BLD-Wall cover | 12/1/2009 | 12/2/2009 | 12/2/2009 | A | PASS |
Tom Arcoraci
|
|
|
wip
|
BLD-Conference | 11/30/2009 | 12/1/2009 | 12/1/2009 | P | PASS |
Tom Arcoraci
|
|
|
|
BLD-Wall cover | 11/19/2009 | 11/24/2009 | 11/24/2009 | A | PASS |
Tom Arcoraci
|
|
|
wip ok
|
BLD-Wall cover | 11/17/2009 | 11/24/2009 | 11/23/2009 | A | CANC |
Tom Arcoraci
|
|
|
|
BLD-Conference | 11/16/2009 | 11/17/2009 | 11/17/2009 | A | PASS |
Tom Arcoraci
|
|
|
|
BLD-Conference | 11/16/2009 | 11/16/2009 | 11/16/2009 | P | PART |
Tom Arcoraci
|
|
|
Herb Phone #: ###-####
|
BLD-Foundation | 9/30/2009 | 9/30/2009 | 9/30/2009 | A | PASS |
Tom Arcoraci
|
|
|
wip ok
|
BLD-Foundation | 9/29/2009 | 9/29/2009 | 9/29/2009 | P | PASS |
Tom Arcoraci
|
|
|
herb Phone #: ###-####
|
BLD-Footing | 9/24/2009 | 9/25/2009 | 9/25/2009 | P | PART |
Tom Arcoraci
|
|
|
wip ok
|
BLD-Footing | 9/23/2009 | 9/24/2009 | 9/24/2009 | A | PASS |
Tom Arcoraci
|
|
|
Herb-1:00 pouring so late am if possible please Phone #: ###-####
|
BLD-Footing | 9/21/2009 | 9/22/2009 | 9/22/2009 | P | PASS |
Tom Arcoraci
|
|
|
herb Phone #: ###-#### wip ok
|