Permit Information
Permit NumberBLD09-00616
StatusFinaled
Name EKC INC
Site Address 1914 S BROADWAY AVE
Project NameGarfield Elementary
Customer Number 
ePlanReviewNo
Description
(GARFIELD ELEMENTARY SCHOOL - RAMP AND ELEVATOR ADDITIONS) Only the basement of this building is fire sprinklered. To construct an exterior concrete ramp and an interior elevator shaft and elevator to serve an existing elementary school. An existing basement stairway and an existing 2nd story stairway will be eliminated. An existing 1st story stairway will be replaced with a new stairway, about 2 feet narrower than the old one. The new elevator will have 5 stops (basement, lower 1st story, upper 1st story, lower 2nd story, and upper 2nd story). For the exterior concrete ramp, work is to include concrete footings, concrete retaining walls, concrete slabs, metal guards, and metal handrails. For the interior elevator, work is to include a masonry shaft for the elevator, a 1-hr elevator machine room, and smoke control on the elevator doors (the elevator doors will open into existing 1-hr corridors). The work is required to comply with the approved drawings, with the plan review report, and with all applicable codes and ordinances. **CJW**
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
BLD-Aging Inspection3/22/20103/22/20103/22/2010 PASS
DetailsJim Storey
DOC - Permit Finaled3/22/20103/22/20103/22/2010PPASS
DetailsJim Storey
FIRE-Final Inspection1/19/20101/19/20101/19/2010APASS
DetailsForrest France
Fire life safety passed.
BLD-Final1/13/20101/14/20101/13/2010APASS
DetailsJim Storey
rick- call 30 mins prior to going Phone #: ###-####
FIRE-Final Inspection12/31/20091/4/20101/5/2010PPASS
DetailsForrest France
Fire life safety is acceptable pending one exit sign at the second level elevator lobby is removed- to be verified prior to structural final approval.
BLD-Final1/4/20101/5/20101/5/2010AFAIL
DetailsJim Storey
Rick-Please call at least 30 mins prior to inspection Phone #: ###-#### need plm final/ need s lable on rated doors 2 locations.
BLD-Conference1/5/20101/5/20101/5/2010AFAIL
DetailsBill VanDegrift
work requireing a plumbing permit has been preformed at this address.
1) secure a plumbing permit- attach this permit to bld09-00616.
2)removecast iron 1/4 bends from relocated 2" waste line and replace with S.S. 90 deg.
3) if the condensate from the new ptac unit is piped to a hub drain in the crawlspace, remove the hub drain, cap waste line and pipe condensate to an approved location.
FIRE-Final Inspection12/30/200912/30/200912/30/2009PCANC
DetailsTroy Cobbley
Cancelled due to time constraints.
BLD-Final12/29/200912/30/200912/30/2009PCANC
DetailsJim Storey
Rick Phone #: ###-#### Inspection cancelled from web by: Patricia Smith
FIRE-Final Inspection12/29/200912/30/200912/30/2009APEND
DetailsForrest France
Final pending project related fire alarm permit.
FIRE-Final Inspection12/7/200912/8/200912/9/2009PNR
DetailsForrest France
See fire code review notes items # 19 and 21. Also IFC 2006 sec. 907.3, 907.3.1.1, 907.2.3, and 903.4.
FIRE-Conference11/4/200911/4/200911/4/2009PDONE
DetailsForrest France
Some issues noted during the project related fire sprinkler cover inspection include: missing electrical supervision of the main control valve for the existing riser-see fire code review note #21, also verify system is current with an annual certification-see note #17, complete protection for the basement per NFPA 13 shall be provided-see note #13- per NFPA 13 2007 sec. 8.6.7.1 sprinklers shall be required in all ceiling pockets unless exceptions 1-7 are met per 8.6.7.2 including item (2) depth of the unprotected pocket does not exceed 36" and item (7) quick response sprinklers are provided throughout the compartment. See also project related fire alarm permit FIR09-00418 review comments items #19, and 6,7, 12 regarding locations of smoke and heat detectors, in particular item #11 referencing NFPA 72 2007 sec. 6.16.4.2 stating heat detectors used for elevator power shut down shall be placed within 2ft of each sprinkler head and be installed per requirements of Chapter 5.
BLD-Other11/2/200911/3/200911/3/2009APASS
DetailsJim Storey
rick - ceiling cover Phone #: ###-#### ok pending others
FIRE-Conference11/2/200911/2/200911/2/2009PDONE
DetailsForrest France
On site visit regarding project attatched fire alarm and sprinkler permit work including coverage at the elevator machine room, monitoring for the existing fire sprinkler riser, fire code review notes, location of the new panel, NFPA 13 and 72 requirements.
BLD-Aging Inspection10/29/200910/29/200910/29/2009 PASS
DetailsJim Storey
wip
BLD-Framing/Rough-in8/24/20098/25/20098/25/2009APASS
DetailsMike Jordan
Rick Phone #: ###-####. Reviewed engineering from Calls engineering on attachment for stair stringer and steel studwall.
BLD-Framing/Rough-in8/21/20098/24/20098/24/2009ACANC
DetailsDave Hannah
rick - please call 1/2 hr prior Phone #: ###-####
BLD-Framing/Rough-in8/18/20098/19/20098/19/2009PPART
DetailsJim Storey
rick Phone #: ###-#### need resolve from mti meetting for epoxy report failled/ ok to gyp all areas but stair stringer wall until support for wall is provited/ tread width needs to be min 11 inches nose to nose.
BLD-Framing/Rough-in8/6/20098/6/20098/6/2009PPASS
DetailsJim Storey
Rick Phone #: ###-#### framing at top of elevator shaft ok headers in walls 1 & 2 ok to cover.
BLD-Framing/Rough-in7/29/20097/30/20097/30/2009PPASS
DetailsJim Storey
Rick Phone #: ###-####