Permit Information
Permit NumberBLD09-00650
StatusFinaled
Name CM COMPANY
Site Address 619 W BANNOCK ST
Project NameAT&T BLDG
Customer Number 
ePlanReviewNo
Description
(QWEST COMMUNICATIONS - 6TH STORY) This building is fire sprinklered for high-rise. To remodel the 6 story of the existing Qwest Communications building. Some nonstructural, nonbearing masonry walls will be removed. Work is to include creating a 1,677 square foot battery room, creating a 2,076 square foot telecommunication equipment room, and combining rooms to create a 897 square foot mechanical room. One-hr fire-resistance-rated fire barrier walls will be constructed. Spill containment for the battery room will be provided. The work is required to comply with the approved drawings, with the plan review report, and with all applicable codes and ordinances. The fire sprinkler system is required to comply with NFPA 13 as regulated by the Fire Department. Spaces used exclusively for telecommunications equipment, associated electrical power distribution equipment, and batteries are not required to be fire sprinklered provided those spaces are equipped throughout with an automatic fire alarm system and are separated from the remainder of the building by fire barriers consisting of not less than 1-hr fire-resistance-rated walls and 2-hr fire-resistance-rated floors (2006 IBC Section 903.2). **CJW**
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
BLD-Final10/26/200910/26/200910/27/2009PPASS
DetailsDave Hannah
Brian Phone #: ###-####
BLD-Final10/22/200910/23/200910/24/2009AFAIL
DetailsDave Hannah
Brian Phone #: ###-#### needs 60 min fire doors
BLD-Final10/21/200910/22/200910/22/2009PCANC
DetailsDave Hannah
Brian Phone #: ###-####
FIRE-Final Inspection10/20/200910/21/200910/21/2009PPASS
DetailsTroy Cobbley
Life safety passed.
FIRE-Final Inspection10/19/200910/20/200910/20/2009ANR
DetailsForrest France
Need project related fire alarm permit final prior to building fire life safety approvals.
BLD-Conference9/18/20099/18/20099/21/2009PPART
DetailsLee Rice
called troy on mechanical because someone in office noticed them working on the roof.
BLD-Framing/Rough-in9/3/20099/4/20099/4/2009APASS
DetailsDave Hannah
Brian Phone #: ###-####