BLD-Final | 9/23/2009 | 9/23/2009 | 9/23/2009 | P | PASS |
Mike Jordan
|
|
|
John Phone #: ###-####. ok for perm occ. Could not find card while on site. Ok for Troy to sign my name on card.
|
FIRE-Final Inspection | 9/23/2009 | 9/23/2009 | 9/23/2009 | P | PASS |
Troy Cobbley
|
|
|
Life safety passed.
|
FIRE-Final Inspection | 9/18/2009 | 9/18/2009 | 9/18/2009 | A | DONE |
Forrest France
|
|
|
Scheduled by a contractor via Hello! on 9/18/2009 at 7:29:56 AM. Contact: ###-####.--Contractor Called and Cancelled///9-18-09 @ 9:25am BAS
|
BLD-Final | 8/27/2009 | 8/27/2009 | 8/27/2009 | A | PART |
Mike Jordan
|
|
|
requesting temp final pending completion of fire corrections issued yesterday. temp approval from fire is complete. Phone #: ###-#### Internet Inspection Request from: John Lodman. ok for temp occ. only.
|
BLD-Final | 8/26/2009 | 8/26/2009 | 8/26/2009 | P | CANC |
Mike Jordan
|
|
|
|
FIRE-Alarm Testing | 8/26/2009 | 8/26/2009 | 8/26/2009 | A | DONE |
Troy Cobbley
|
|
|
See previous entry.
|
FIRE-Final Inspection | 8/26/2009 | 8/26/2009 | 8/26/2009 | A | PART |
Troy Cobbley
|
|
|
A temporary occupancy is being given with scott and marks approval. The remaining items are provide additional emergency lighting as marked on the electrical sheet, provide missing hardware and exit signs in the board room, provide occupant load signs for the conference rooms, provide correct smoke detector coverage in room 176, provide verification that the velocity listing for the underfloor detectors has not been exceeded, provide maps at both fire panels as discussed and test the server room liebert units for shutdown.
|
BLD-Final | 8/26/2009 | 8/26/2009 | 8/26/2009 | A | NR |
Mike Jordan
|
|
|
requesting temp occupancy with balance of interior doors as only exception. door install in progress. Phone #: ###-#### Internet Inspection Request from: John Lodman
|
FIRE-Final Inspection | 8/25/2009 | 8/25/2009 | 8/25/2009 | P | CANC |
Troy Cobbley
|
|
|
The life safety could not be completed due to time constraints and the project related fire alarm and fire sprinkler permits not being completed. I also noted that several doors/hardware had not been installed.
|
FIRE-Alarm Testing | 8/25/2009 | 8/25/2009 | 8/25/2009 | P | CANC |
Troy Cobbley
|
|
|
The life safety could not be completed due to time constraints and the project related fire alarm and fire sprinkler permits not being completed. I also noted that several doors/hardware had not been installed.
|
BLD-Other | 8/20/2009 | 8/21/2009 | 8/21/2009 | P | PART |
Mike Jordan
|
|
|
ceiling cover north of grid 3.5 please. Phone #: ###-#### Internet Inspection Request from: John Lodman. Pend. elec. ri.
|
BLD-Other | 8/18/2009 | 8/19/2009 | 8/19/2009 | A | PART |
Mike Jordan
|
|
|
ceiling cover south of grid 3.5. pending trade inspection should be complete this morning. Phone #: ###-#### Internet Inspection Request from: John Lodman. Grid ok, south half. Noted to general contractor that their is no occupancy allowed at this time. Noted employees with offices set up and working.
|
BLD-Other | 8/18/2009 | 8/18/2009 | 8/18/2009 | P | NR |
Mike Jordan
|
|
|
ceiling cover south of gridline 3.5 please Phone #: ###-#### Internet Inspection Request from: John Lodman
|
BLD-Other | 8/6/2009 | 8/7/2009 | 8/7/2009 | A | PART |
Jim Sly
|
|
|
Ceiling cover in room 176-data only. elec and fire sprink pending this a.m. thank you. Phone #: ###-#### Internet Inspection Request from: John Lodman Data room OK. After Fire and Ele OK'd
|
BLD-Wall cover | 7/28/2009 | 7/28/2009 | 7/28/2009 | P | PASS |
Mike Jordan
|
|
|
John center of building Phone #: ###-####. INterior steel stud framed walls at center portion. no grid.
|
BLD-Framing/Rough-in | 7/22/2009 | 7/23/2009 | 7/23/2009 | A | PART |
Mike Jordan
|
|
|
AM electrical inspection pending. Requesting approval to cover walls south of approx gridline 3.5 and north of approx gridline 5.3. no plumbing inspection required in these areas to be covered as plumbing is all existing. Phone #: ###-#### Internet Inspection Request from: John Lodman. INterior steel stud framed walls only at north and south ends od bldg. wip on center portion.
|