Information based on query as of Wednesday, July 17, 2024.
Permit Information
Permit NumberBLD09-01275
StatusFinaled
Name CONTRACTORS NORTHWEST
Site Address 130 N MILWAUKEE ST
Project NamePETSMART
Customer Number 
ePlanReviewNo
Description
(PETSMART TENANT IMPROVEMENT) This building is required to be fire sprinklered for building area increase. To construct interior tenant improvements within a new building shell for a pet store. This tenant space will be used for retail sales, pet salon, pet medical treatment, and pet boarding. The building shell was constructed under permit BLD09-01007. Work is to include interior nonbearing walls, interior doors, interior windows, 2 restrooms accessible to the disabled, suspended acoustical ceilings, millwork, and finishes. The work is required to comply with the approved drawings, with the plan review report, and with all applicable codes and ordinances. The fire sprinkler system is required to comply with NFPA 13 as regulated by the Fire Department. A separate permit is required for high-rack storage. **CJW**
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
BLD-Final5/26/20105/27/20105/27/2010APASS
DetailsMike Jordan
ok for perm occ.
FIRE-Final Inspection5/7/20105/10/20105/10/2010PPASS
DetailsTroy Cobbley
Life safety passed.
BLD-Final5/6/20105/7/20105/7/2010APASS
DetailsMike Jordan
Rod Phone #: ###-####. ok for temp. occ. Open plumbing permit should be stand alone permit. Needs to complete firecaulking at riser room and repair the doorhardware at the pet salon.
FIRE-Final Inspection5/5/20105/6/20105/6/2010APART
DetailsTroy Cobbley
A temporary occupancy was given with Scott and Marks approval until the fire alarm permit for the new tamper switch on the anti-freeze loop has been finaled. The work has been scheduled for monday morning at 8:00am.
FIRE-Conference5/6/20105/6/20105/6/2010ADONE
DetailsTroy Cobbley
The property manager, Linda, contacted me about a temporary occupancy for this project until Monday due to SimpleGrinnell not being able to perform their work until that I deferred her to Mark Senteno for a decision.
FIRE-Final Inspection5/3/20105/4/20105/4/2010PFAIL
DetailsTroy Cobbley
The project related fire alarm permit needs to be finaled, verification of factory installed duct smoke detectors and the indicators installed on the main exit doors as discussed. The previous items have been corrected.
BLD-Final4/29/20104/30/20104/30/2010ANR
DetailsMike Jordan
rod Phone #: ###-####. Also spoke to contractor about shell and core permit.
FIRE-Final Inspection4/28/20104/29/20104/29/2010PFAIL
DetailsTroy Cobbley
The project related fire alarm permit needs to be finaled. Also indicators and stickers need to be installed at the two sets of double main entry doors. The exit discharge light on the northwest exit door did not function.
FIRE-Conference4/14/20104/14/20104/14/2010PDONE
DetailsTroy Cobbley
I spoke with the job superintendant for CNI Construction about the need for an additional fire alarm permit for the connection of the canopy anti-freeze system control valve into the existing fire alarm system located at 104 Milwaukee. This fire alarm work is not covered under the new PetsMart fire alarm system. I let him know that I could not sign off on the building until this additional permit has atleast been submitted for review. He said he would let the associated parties know.
BLD-Other4/7/20104/8/20104/8/2010APASS
DetailsMike Jordan
rob - ceiling grid Phone #: ###-####. Reinspected grid ceiling. grid as installed per cisca 0-2 ok. Received letter from CASCO (architect of record) noting that CISCA 0-2 system is approved to be installed in leiu of the CICSCA3-4. Will have letter scanned into project.
BLD-Conference4/5/20104/5/20104/5/2010PDONE
DetailsMike Jordan
Met on site with contractor to discuss ceiling grid issues. Will discuss with plan reviewer before proceeding further.
BLD-Framing/Rough-in3/31/20103/31/20103/31/2010PFAIL
DetailsMike Jordan
Ceiling grid inspection please-Rod- Phone #: ###-####. Installed grid not per plan.
BLD-Energy code compliance3/1/20103/2/20103/2/2010APASS
DetailsMike Jordan
Rod Phone #: ###-####
BLD-Framing/Rough-in2/25/20103/1/20103/1/2010APASS
DetailsMike Jordan
ROD Phone #: ###-####. All interior steel stud framed walls and backing for ada elements, no grid. Also spoke to rod about 1hr. consttruction requirements for fire riser room.
BLD-Aging Inspection2/24/20102/24/20102/24/2010 PASS
DetailsMike Jordan
work is in progress on interior steel stud walls. Visited job site last week. Should be ready for framing inspection by early next week as per contractor.