BLD-Final | 8/31/2010 | 9/1/2010 | 9/1/2010 | A | PASS |
Tom Arcoraci
|
|
|
Travis Phone #: ###-####
|
FIRE-Final Inspection | 8/31/2010 | 8/31/2010 | 9/1/2010 | P | PASS |
Troy Cobbley
|
|
|
Life safety passed
|
BLD-Final | 8/26/2010 | 8/26/2010 | 8/26/2010 | P | PART |
Tom Arcoraci
|
|
|
travis Phone #: ###-#### ok after fire sign off
|
FIRE-Final Inspection | 8/26/2010 | 8/26/2010 | 8/26/2010 | P | FAIL |
Troy Cobbley
|
|
|
An outside supply duct has been added to the unit. This new duct is connected to the hvac unit before the duct detector which would delute any smoke from within the compartment. This new ducting needs to be connected to the hvac unit after the duct smoke detector. No testing was performed.
|
FIRE-Final Inspection | 8/24/2010 | 8/24/2010 | 8/25/2010 | P | FAIL |
Troy Cobbley
|
|
|
The west hvac unit tested ok. The east hvac unit would not go into heat mode like it did the day before so that it could be tested.
|
BLD-Final | 8/24/2010 | 8/24/2010 | 8/24/2010 | P | NR |
Tom Arcoraci
|
|
|
Kent Phone #: ###-####
|
FIRE-Final Inspection | 8/20/2010 | 8/23/2010 | 8/23/2010 | A | FAIL |
Troy Cobbley
|
|
|
The east side duct smoke detector did not shut down the hvac unit immediately when tested. The west side hvac unit would not turn on for the testing.
|
BLD-Final | 8/20/2010 | 8/23/2010 | 8/23/2010 | A | NR |
Tom Arcoraci
|
|
|
travis Phone #: ###-####
|
BLD-Final | 7/23/2010 | 7/26/2010 | 7/26/2010 | P | PART |
Tom Arcoraci
|
|
|
James Phone #: ###-#### needs fire sign off
|
FIRE-Final Inspection | 7/23/2010 | 7/26/2010 | 7/26/2010 | A | FAIL |
Troy Cobbley
|
|
|
Upon review of the city approved plans there are two duct smoke detectors shown on the Mechanical sheets and they are installed as well. These two detectors will be required to be tested with the required remote annunciators or have engineer approval to delete since the drawings show the units at only 1700 cfm. All other items are ok.
|
FIRE-Final Inspection | 7/22/2010 | 7/22/2010 | 7/22/2010 | P | FAIL |
Troy Cobbley
|
|
|
Provide city approved plans, provide address and fire extinguisher as discussed.
|
BLD-Final | 7/21/2010 | 7/22/2010 | 7/22/2010 | A | NR |
Tom Arcoraci
|
|
|
call 30 min prior to meet//Travis Shelton Phone #: ###-####
|
BLD-Aging Inspection | 6/22/2010 | 6/22/2010 | 6/22/2010 | | PASS |
Tom Arcoraci
|
|
|
|
BLD-Framing/Rough-in | 4/21/2010 | 4/22/2010 | 4/22/2010 | P | PART |
Tom Arcoraci
|
|
|
shane Phone #: ###-#### check truss buckets for girder at next inspection
|
BLD-Foundation | 3/18/2010 | 3/19/2010 | 3/19/2010 | A | PASS |
Tom Arcoraci
|
|
|
Re-enforcing-rebar inspection Phone #: ###-#### strata on site
|
BLD-Footing | 3/18/2010 | 3/18/2010 | 3/18/2010 | P | PASS |
Tom Arcoraci
|
|
|
Re-enforcing-rebar inspection Phone #: ###-#### strata on site
|