BLD-Final | 12/14/2009 | 12/15/2009 | 12/15/2009 | P | PASS |
Dave Hannah
|
|
|
Mike Phone #: ###-#### ok for perm occ
|
FIRE-Final Inspection | 12/11/2009 | 12/14/2009 | 12/14/2009 | P | PASS |
Forrest France
|
|
|
C/N items done, fire life safety passed.
|
FIRE-Final Inspection | 12/9/2009 | 12/9/2009 | 12/9/2009 | P | FAIL |
Forrest France
|
|
|
Missing max. occupant load sign, provide one "K class" extinguisher for the kitchen, post suite address numbers, remove surface mounted hasp locks at three locations, provide certification of a current annual inspection for the fire sprinkler system, the type one hood suppression system needs modification to properly cover new appliance layout (permit required for modifications). See list of general conditions on permit documents for details.
|