FIRE-Final Inspection | 4/7/2010 | 4/7/2010 | 4/7/2010 | A | PASS |
Forrest France
|
|
|
Correction notice item finished, fire life safety final approved.
|
BLD-Other | 4/7/2010 | 4/7/2010 | 4/7/2010 | A | DONE |
Forrest France
|
|
|
On site functional testing of the relocated automatic fire door completed satisfactory and within allowable closure rates per NFPA 80.
|
BLD-Final | 4/7/2010 | 4/7/2010 | 4/7/2010 | A | PASS |
Jim Storey
|
|
|
final ok card not avalable to sign.
|
BLD-Other | 4/7/2010 | 4/7/2010 | 4/7/2010 | A | PASS |
Jim Storey
|
|
|
fire door actuation test.
|
BLD-Conference | 4/6/2010 | 4/6/2010 | 4/6/2010 | A | PASS |
Jim Storey
|
|
|
|
BLD-Conference | 4/5/2010 | 4/6/2010 | 4/6/2010 | P | CANC |
Jim Storey
|
|
|
|
FIRE-Final Inspection | 3/26/2010 | 3/26/2010 | 3/26/2010 | A | PART |
Forrest France
|
|
|
ref. NFPA 80 regarding min. and max closure rate for the relocated fire door- (6"/sec. - 24"/sec.).
|
BLD-Final | 3/25/2010 | 3/25/2010 | 3/25/2010 | P | PART |
Jim Storey
|
|
|
mike Phone #: ###-#### ti ok to occupnance work on fire shudder in progress. temp isued.
|
FIRE-Final Inspection | 3/24/2010 | 3/25/2010 | 3/25/2010 | A | PART |
Forrest France
|
|
|
Fire life safety inspection completed satisfactory, noted corrections finished within the tenant space. Final pending completion and testing of the relocated automatic fire door at the exterior canopy per scope of pemit work.
|
FIRE-Conference | 3/24/2010 | 3/24/2010 | 3/24/2010 | P | DONE |
Forrest France
|
|
|
On site visit regarding fire life safety inspection items including exit signs, EM lights, door hardware, etc.
|
BLD-Conference | 3/24/2010 | 3/24/2010 | 3/24/2010 | A | PASS |
Jim Storey
|
|
|
door being relocated
|
BLD-Conference | 3/22/2010 | 3/22/2010 | 3/22/2010 | A | PASS |
Jim Storey
|
|
|
reviewed relocation of 2 hr fire shudder for compliant applacation to protect canopy opening.
|
BLD-Framing/Rough-in | 3/16/2010 | 3/17/2010 | 3/17/2010 | A | PASS |
Jim Storey
|
|
|
mike Phone #: ###-####
|