Permit Information
Permit NumberBLD10-01058
StatusFinaled
Name VERTICAL CORP
Site Address 306 S 6TH ST
Project NameIntegrated Design Lab
Customer Number 
ePlanReviewNo
Description
(INTEGRATED DESIGN LAB) PLAN MODIFICATION, 1/18/11, EXPANDING SCOPE OF WORK TO INCLUDE STRUCTURAL SUPPORT UPGRADE OF ROOF STRUCTURE ALONG GRIDLINE 'F' BETWEEN GRID POINT 3.8 TO 7, ADJACENT TO NEW CONCORDIA UNIVERSITY, IN ACCORDANCE WITH SUBMITTED STRUCTURAL ENGINEERING DESIGN CALCS & DETAILS. REMAINDER OF PERMIT AND ALL ATTACHMENTS REMAIN AS ORIGINALLY APPROVED. DRS Remodel a 2,640 sq. ft. portion of the 8,714 sq. ft. shell space created under BLD10-00902 for use by Integrated Design Lab as an office, testing & training facility per the reviewed plans. Compliance with building code for restroom and drinking fountain requirements are part of BLD10-01061 which creates common core area facilities. Work to include select interior demolition; perform structural modifications to portions of roof for new skylights and HVAC units; construction of 2-hour fire barrier walls around the open office / conference room to create a separate 2,118 sq. ft. fire area ( designated as fire area 1B on plans) containing an "A3" occupancy so a fire suppression system is not required. The fire barrier walls will also be a part of a required 1-hour fire rated common exit corridors that will serve this tenant space, existing tenants and future tenant spaces. All doors serving as part of the egress system from the "A3" assembly occupancy to the exit discharge shall be panic hardware if door hardware is provided. Modify electrical, mechanical, plumbing, interior finishes and millwork. Install new stairway at the end of and as part of the rated corridor system created under BLD10-01061 designated on plans as corridor 107 & stair 108. drs
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
BLD-Aging Inspection6/17/20146/17/20146/24/2014 PASS
DetailsDave Hannah
DOC - Permit Finaled6/24/20146/24/20146/24/2014PPASS
DetailsDave Hannah
BLD-Aging Inspection3/18/20143/18/20143/19/2014 PEND
DetailsDave Hannah
BLD-Aging Inspection11/14/201311/14/201311/22/2013 PASS
DetailsDave Hannah
BLD-Aging Inspection2/26/20132/26/20133/1/2013 PASS
DetailsDave Hannah
BLD-Other4/19/20114/20/20114/20/2011ANR
DetailsDave Hannah
jerry - structrual steel inspection Phone #: ###-#### needs to get specal inspection items cleaned up and finish bolting
BLD-Aging Inspection4/6/20114/6/20114/7/2011 DEFR
DetailsDave Hannah
waiting on them to start
BLD-Final1/31/20112/1/20112/1/2011APART
DetailsDave Hannah
Wants temp occ plan mod still in review---Jerry-###-#### ok for temp occ
FIRE-Final Inspection1/31/20111/31/20111/31/2011PPASS
DetailsForrest France
C/N items finished, max. occupant load sign to be posted as discussed.
FIRE-Final Inspection1/27/20111/28/20111/28/2011AFAIL
DetailsForrest France
Post two fire extinguishers as discussed, install one exit sign at the second classroom exit door per plan. Mechanical inspector to review damper installation.
FIRE-Final Inspection1/27/20111/27/20111/27/2011PCANC
DetailsForrest France
###-#### - jerry//cancelled by Jerry and rescheduled for tomorrow AM--1/27/11 11:57am leg
BLD-Other12/13/201012/14/201012/14/2010APASS
DetailsJim Storey
Jerry this is for fire wall inspection Phone #: ###-#### ok for 2 nd layer per plan.
BLD-Conference12/8/201012/9/201012/9/2010APASS
DetailsDave Hannah
jerry Phone #: ###-#### shaft wall on back side of two hr wall ok to cover
BLD-Framing/Rough-in12/8/201012/9/201012/9/2010APASS
DetailsDave Hannah
jerry Phone #: ###-#### ceiling framing ok also shaft wall on back side of two hr wall ok to cover
FIRE-Conference12/8/201012/9/201012/9/2010ADONE
DetailsForrest France
Regarding smoke detectors at new dampers in the rated wall.
BLD-Conference11/30/201012/1/201012/1/2010APASS
DetailsDave Hannah
Jerry Phone #: ###-#### ok to build a 2hr sheetrock assembly between roof joist