BLD-Final | 7/26/2010 | 7/27/2010 | 7/27/2010 | A | PASS |
Tom Arcoraci
|
|
|
Hasmukh Phone #: ###-####
|
FIRE-Final Inspection | 7/26/2010 | 7/26/2010 | 7/26/2010 | P | PASS |
Troy Cobbley
|
|
|
Life safety passed.
|
BLD-Final | 7/20/2010 | 7/21/2010 | 7/21/2010 | P | NR |
Tom Arcoraci
|
|
|
Hasmukh Phone #: ###-#### needs fire sign off
|
FIRE-Final Inspection | 7/20/2010 | 7/21/2010 | 7/21/2010 | A | FAIL |
Troy Cobbley
|
|
|
Remove the thumbturn lock from the main exit, provide automatic flush bolts at the main exit and remove the manual flush bolts, provide exit signs and emergency lights as per the approved plans, lower the fire extinguisher to less than 5', provide an additional fire extinguisher in the retail area or relocate the existing fire extinguishers so that travel does not exceed 75', repair the emergency light in the basement, the secondary exit door is required to swing out, have compliant hardware and have the dead bolts removed. I also noted that a motorized conveyor is installed on the stairs to the basement storage area and the required 36" minimum egress is gone.
|