BLD-Final | 6/16/2011 | 6/17/2011 | 6/17/2011 | A | PASS |
Jim Storey
|
|
|
Martin Phone #: ###-#### final ok perm occ. not able to sign card.
|
BLD-Final | 4/5/2011 | 4/6/2011 | 4/6/2011 | A | PART |
Jim Storey
|
|
|
martin Phone #: ###-#### temp ok
|
FIRE-Final Inspection | 4/4/2011 | 4/5/2011 | 4/5/2011 | A | PASS |
Forrest France
|
|
|
Corrections finished. Fire life safety passed.
|
FIRE-Final Inspection | 3/31/2011 | 4/1/2011 | 4/1/2011 | P | PART |
Forrest France
|
|
|
Correction items verified for completion. Final pending repair of an exit sign and one non-functional damper motor at the 3rd floor.
|
FIRE-Final Inspection | 3/31/2011 | 3/31/2011 | 3/31/2011 | P | PART |
Forrest France
|
|
|
Corrections underway.
|
FIRE-Final Inspection | 3/29/2011 | 3/30/2011 | 3/30/2011 | P | NR |
Forrest France
|
|
|
Preliminary life safety inspection completed including UPS and emergency generator tests, noted areas on each floor in need of adjustments in exit signage placement and EM lighting, noted hardware at two doors to be switched, discussed fire extinguishers, building address, occupant load signs, review notes, project schedule, fire alarm work, etc.
|
BLD-Framing/Rough-in | 3/15/2011 | 3/16/2011 | 3/16/2011 | P | PASS |
Jim Storey
|
|
|
martin - ceiling grid Phone #: ###-####
|
BLD-Other | 3/14/2011 | 3/15/2011 | 3/15/2011 | A | FAIL |
Jim Storey
|
|
|
Ceiling grid basement--Martin Phone #: ###-#### seal coridor penatrations.
|
BLD-Other | 3/8/2011 | 3/8/2011 | 3/8/2011 | P | PART |
Jim Sly
|
|
|
martin (this is for the first floor) Phone #: ###-#### Ceiling Grid 1st floor OK ...Except for Corridors.
|
FIRE-Conference | 2/24/2011 | 2/24/2011 | 2/24/2011 | P | DONE |
Forrest France
|
|
|
Regarding project related fire alarm work.
|
BLD-Other | 2/18/2011 | 2/22/2011 | 2/22/2011 | A | PASS |
Jim Storey
|
|
|
ceiling grid insp for 3rd floor//Martin Phone #: ###-#### all ceillings ok pending others.
|
BLD-Framing/Rough-in | 1/20/2011 | 1/21/2011 | 1/21/2011 | P | PASS |
Jim Storey
|
|
|
martin Phone #: ###-#### first floor ok to cover.
|
BLD-Framing/Rough-in | 1/14/2011 | 1/18/2011 | 1/18/2011 | P | PASS |
Jim Storey
|
|
|
Martin ###-####
|