BLD-Final | 10/14/2011 | 10/17/2011 | 10/17/2011 | P | PASS |
Dave Hannah
|
|
|
All other inspections have been done. Scott Phone #: ###-#### >> Inspection requested via web by Scott Asin
|
FIRE-Final Inspection | 10/13/2011 | 10/14/2011 | 10/14/2011 | P | PASS |
Troy Cobbley
|
|
|
Life safety passed
|
BLD-Conference | 10/5/2011 | 10/6/2011 | 10/6/2011 | P | NR |
Jim Sly
|
|
|
I am ready for the fire/life safety inspection. I have the approved plans and sign-off card onsite by the back set of stairs. Phone #: ###-#### >> Inspection requested via web by Scott Asin
|
FIRE-Final Inspection | 10/6/2011 | 10/6/2011 | 10/6/2011 | A | FAIL |
Forrest France
|
|
|
Noted missing exit signs and EM lighting per plan at the 2nd, 1st and basement levels- see A and E sheets on stamped plan set for locations, remove cover at the FACP smoke detector, repair one non-functional light at an EM adjacent to the restrooms, remove non-required signage at 2nd floor door 29, door 8e appears to need hardware group 4, provide approved hardware at the bar door to basement stairs.
|
FIRE-Final Inspection | 10/6/2011 | 10/6/2011 | 10/6/2011 | A | FAIL |
Forrest France
|
|
|
See plan annotations.
|
FIRE-Final Inspection | 10/5/2011 | 10/6/2011 | 10/5/2011 | A | CANC |
Forrest France
|
|
|
I am ready for the fire/life safety inspection. Phone #: ###-#### >> Inspection requested via web by Scott Asin Inspection cancelled from web by: Scott Asin
|
BLD-Framing/Rough-in | 9/7/2011 | 9/8/2011 | 9/8/2011 | A | PASS |
Dave Hannah
|
|
|
scott please look at celing and the old bathroom and office area Phone #: ###-####
|
BLD-Framing/Rough-in | 9/7/2011 | 9/7/2011 | 9/7/2011 | P | PART |
Dave Hannah
|
|
|
scott please look at celing and the old bathroom and office area Phone #: ###-#### needs to fire block furred out wall and add metal stapes to ceiling
|
FIRE-Conference | 8/31/2011 | 8/31/2011 | 8/31/2011 | P | DONE |
Forrest France
|
|
|
Regarding project schedule and related FIR trade permit work.
|
FIRE-Conference | 8/15/2011 | 8/16/2011 | 8/16/2011 | A | DONE |
Forrest France
|
|
|
We are getting ready to open the wall between the two halves of the building. I would like to have you take a look around to see if we missed anything. Once the new bathrooms are being used, we will go in and remove the old bathrooms, office and stage. This is kind of a partial final inspection I guess. Thanks. Scott Phone #: ###-#### >> Inspection requested via web by Scott Asin
|
BLD-Conference | 8/15/2011 | 8/15/2011 | 8/16/2011 | P | PART |
Dave Hannah
|
|
|
We are ready to start using the new bathrooms and opening up the temp wall between the two halves of the building. I would like to check with you to see if you are okay with that. Phone #: ###-#### >> Inspection requested via web by Scott Asinok to use back area after other trades ok
|
BLD-Framing/Rough-in | 6/20/2011 | 6/21/2011 | 6/21/2011 | A | PASS |
Dave Hannah
|
|
|
HVAC, Electrical and Plumbing are all inspected. Phone #: ###-#### >> Inspection requested via web by Scott Asin
|