BLD-Final | 6/1/2011 | 6/1/2011 | 6/1/2011 | P | PART |
Mike Jordan
|
|
|
Jim Phone #: ###-####. Ok for temp occ. Will be ok for perm occ once plumbing finals.
|
BLD-Final | 5/31/2011 | 5/31/2011 | 5/31/2011 | P | FAIL |
Mike Jordan
|
|
|
jim - late afternoon please Phone #: ###-####. Install all ada signage, also no grid inspection.
|
FIRE-Final Inspection | 5/31/2011 | 5/31/2011 | 5/31/2011 | P | PASS |
Forrest France
|
|
|
Fire life safety inspection passed.
|
FIRE-Conference | 5/31/2011 | 5/31/2011 | 5/31/2011 | A | DONE |
Forrest France
|
|
|
Discussion with contractor regarding items for final including repair two exit sign/EM lights, post max. occupant load sign, post PFE with current tag, add one exit sign per plan at restroom hall, test EM lights at grid ceilings, provide verification fire sprinkler system is current with an annual inspection.
|
BLD-Framing/Rough-in | 5/12/2011 | 5/12/2011 | 5/12/2011 | A | PART |
Mike Jordan
|
|
|
Phone #: 5413312871 >> Inspection requested via mobile web by jim wellman. Interior steel stud framed walls only, no grid and pending elec. inspection. Also needs to provide engineering showing that the existing roof trusses can support the additional load on them fro the additional framing. Also noted that plans call for seperated uses, and notes 1hr. fire walls on either side. New wall on vanilla finish was not inspected as a 1hr. fire wall. Either provide UL for new wa;;, remove one side for proper inspection or resubmit plans to plan review for non seperated use. Correction notice was issued.
|